  <item>
    <title>CSI Division 26 - Electrical, Section 26 36 23 - 600 Volt Automatic Transfer Switches - MS050913</title>
    <description>
      Revised 1.01 E. to read as, &quot;Section 26 23 13 – 600 Volt Generator Paralleling Switchgear&quot;. Revised 1.03 C. 8 to read as, &quot;IEEE 446 - IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications&quot;. Revised 1.03 C. 10 to read as, &quot;IEEE 666 – Design Guide for Electric Power Service Systems for generating Stations&quot;. Added 10.7 A to require, &quot;COORDINATION WITH UTILITY COMPANY A. The Contractor shall, on behalf of the Owner, coordinate with utility company in providing required information for reviewing and assuring that installation will meet utility requirements as well as Electric Substantive Rules set forth by Public Utility Commission of Texas, which governs technical requirements for interconnection and parallel operation of on-site distributed generation and utility company distributed generation. Added 2.03 L to require, &quot;L. Closed transition. When designing a closed-transition system, it is imperative that the system be designed with interlocks that prevent the inadvertent and indefinite paralleling of sources. The following design rules should be used when designing closed-transition system. 1. Closed-transition switchgear should be designed such that manual transfers are manually initiated and automatically interlocked. This prevents utility sources from being paralleled for an excessive amount of time. This transition shall take place within the range of 100 milliseconds, depending on specific utility requirements. 2. Closed-transition switchgear should be designed with a non-defeatable safety-circuit timing relay, which will cause source disconnection within a predetermined time if the sources are manually paralleled, or the closed-transition interlocking scheme fails to perform. For example, a timing relay that opens the tie breaker if both utility mains are closed for 10 sec would serve this function. 3. Where closed-transition automatic transfer switches are specified, a shunt-trip circuit breaker on the normal feeder could be specified to force the normal feeder to open in the case of a failed-closed transition. 4. All of the functions noted in 1-3 above should be alarmed and annunciated.
      &quot;
      - Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2036%2023.doc</link>
    <guid isPermaLink="false">26 36 23 MS050913</guid>
    <pubDate>Thu, 09 May 2013 08:27:15 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS041113</title>
    <description>
      Revised 2.02 A. to read as, &quot;Conduit marking. Externally mark all conduits for feeders, branch circuits using the same circuit designations as indicated on construction drawings and final as-built documents. Such marks shall be made at the point of origin and destination of the conduits, using permanent marker.&quot;  Revised the first two sentences of 2.02 F. to read as, &quot;Panelboards: Prepare a neatly typed circuit directory printed on 80 weight paper. This directory shall be installed behind clear heat-resistant plastic in a metal frame tack welded to the inside of the door for each panelboard.&quot;
      - Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS041113</guid>
    <pubDate>Thu, 11 Apr 2013 08:40:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 27 26 - Wiring Devices - MS041113</title>
    <description>
      Revised the parts number for Pass &amp; Seymour 5-20R (Duplex) recetracle to read as
      &quot;8300&quot;. Paragraph 2.04 D.
      - Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2027%2026.doc</link>
    <guid isPermaLink="false">26 27 26 MS041113</guid>
    <pubDate>Thu, 11 Apr 2013 08:40:09 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG011513</title>
    <description>
      Added requirement that ATS shall be closed transition type.
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r08/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG011513</guid>
    <pubDate>Thu, 17 Jan 2013 08:37:12 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 36 23 - Automatic Transfer Switches - MS011513</title>
    <description>
      Added requirement that ATS shall be closed transition type and various other revisions throughout document.
      Paragraphs 1.01C,D and E; 1.03C.2; 1.04; 1.06; 2.01 B; 2.03 K; 2.04 H; 3.01 E,F,G,H and I; 3.02 C,D and E; 3.03.
      - Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2036%2023.doc</link>
    <guid isPermaLink="false">26 36 23 MS011513</guid>
    <pubDate>Thu, 17 Jan 2013 08:37:10 CDT</pubDate>
  </item>
  
  <item>
    <title>Electrical Design Guideline Element D5000 - Load Calculation Criteria - ODG121312</title>
    <description>
      Added requirement of &quot;Arch Flash Analysis shall be provided per the requirements of applicable edition of NFPA 70E. Arch Flash hazard warning signs and labels shall be in conformance with MD Anderson specification.&quot; Paragraph 3.01 B.
      - Please direct Questions and Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D5000-M.pdf</link>
    <guid isPermaLink="false">D5000 ODG121312</guid>
    <pubDate>Thu, 13 Dec 2012 08:36:05 CDT</pubDate>
  </item>

  <item>
    <title>Element D5034 - Nurse Call / Communication Systems - ODG121312</title>
    <description>
      General Electric now reflects Ascom as C600 Nurse Call system provider due to buy out of product line by Ascom. Attachment “A” - added P12 under Telligence System.
      - Please direct Questions and Comments to Tim LeCuyer at 713-563-5030.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r04/D5034-M.pdf</link>
    <guid isPermaLink="false">D5034 ODG121312</guid>
    <pubDate>Thu, 13 Dec 2012 08:36:03 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 33 53 - Three-Phase Uninterruptible Power Systems - MS121312</title>
    <description>
      Initial adoption and posting of specification section.
       - Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2033%2053.doc</link>
    <guid isPermaLink="false">26 33 53 MS121312</guid>
    <pubDate>Thu, 13 Dec 2012 08:36:00 CDT</pubDate>
  </item> 
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 23 00 - 600 Volt Switchgear - MS110612</title>
    <description>
      Revised the section title to read as &quot;600 Volt Switchgear&quot;. Added 2.07 D. 1. to require &quot;Main breakers shall have a Reduced Energy Let-Thru (RELT) setback mode controlled by a key switch installed in the switchgear main breaker section. The RELT setback mode switch shall adjust the trip and time delays setting on all main breakers in the gear lineup to minimum values to limit arc flash hazard levels. An indicator at each main breaker and blue beacon on top of switchgear, which shall illuminate when the RELT setback mode is activated. Added 2.07 D. 2. to require &quot;Main breaker sections/compartments shall be equipped with infrared scanning windows, which allow thermographic scan viewing of all lugs and bolted connections within this section without having to open any enclosure panels to allow thermogrphic scans of electrical connections.&quot;
       - Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2023%2000.doc</link>
    <guid isPermaLink="false">26 23 00 MS110612</guid>
    <pubDate>Tue, 06 Nov 2012 08:39:12 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 36 25 - 5kV Emergency Generator Paralleling Switchgear - MS110612</title>
    <description>
      Added 2.14 H. 1. to require &quot;Main breaker sections/compartments shall be equipped with infrared scanning windows, which allow thermographic scan viewing of all lugs and bolted connections within this section without having to open any enclosure panels to allow thermogrphic scans of electrical connections.&quot;
      - Please direct Questions an Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2036%2025.doc</link>
    <guid isPermaLink="false">26 36 25 MS110612</guid>
    <pubDate>Tue, 06 Nov 2012 08:39:11 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS082812</title>
    <description>
      Revised 2.02 G. 2. to read as &quot;Emergency circuit junction boxes and their covers shall be painted red. Circuit identification shall be marked on the junction box cover.&quot;
       - Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS082812</guid>
    <pubDate>Tue, 28 Aug 2012 08:33:24 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS082812</title>
    <description>
      Revised 3.02 C. 1. to read as &quot;Install electrical cable, wire and connectors as indicated.  All installations, temporary or permanent, shall be in accordance with the manufacturer’s written instructions, the applicable requirements of NEC, and as required ensuring that products serve the intended functions.&quot;
       - Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
    <guid isPermaLink="false">26 05 19 MS082812</guid>
    <pubDate>Tue, 28 Aug 2012 08:33:23 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Cable Trays, and Boxes - MS082812</title>
    <description>
      Revised 3.01 E. to read as &quot;Support all conduits and J-boxes above ceilings from the building structure.  All J-boxes being installed above suspended ceilings must have a minimum of 12-inch working clearance  between the bottom of J-boxes and the top of the ceiling grid except where approved by the Owner in writing prior to installation.&quot;
       - Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS082812</guid>
    <pubDate>Tue, 28 Aug 2012 08:33:22 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D5034 - Nurse Call / Communication Systems - ODG062812</title>
    <description>
      Element re-titled; reformatted sections to include:  General Design Criteria, Design Criteria for Outpatient and Surgery Areas; revised Special Contract Document Requirements; expanded and revised Products section – updated manufacturers and product data.
      Please direct Questions and Comments to Tim LeCuyer at 713-563-5030.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D5034-M.pdf</link>
    <guid isPermaLink="false">D5034 ODG062812</guid>
    <pubDate>Thu, 28 Jun 2012 08:35:16 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS061912</title>
    <description>
      Editorial correction to eliminate the discrepancies where one place calls for minimum &#35;14 wire for control circuit, while the other requires minimum &#35;12 wire. Paragraph 2.01 B, 3.02 C. 5.
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
    <guid isPermaLink="false">26 05 19 MS061912</guid>
    <pubDate>Tue, 19 Jun 2012 08:41:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D501001 - Electrical System for Telecommunications Rooms - ODG061412</title>
    <description>
      2.01 C:  Changed &quot;3 feet above finished floor&quot; to &quot;the surface of finished floor&quot;, aligning with the requirement of Element D5030 2.03 O.
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D501001-M.pdf</link>
    <guid isPermaLink="false">D501001 ODG061412</guid>
    <pubDate>Thu, 14 Jun 2012 08:23:31 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D5020 - Lighting and Branch Wiring - ODG061412</title>
    <description>
      2.01 A. 1: Changed &quot;latest&quot; to &quot;applicable&quot;.
      2.01 B. 1:  Changed &quot;Z2050&quot; to &quot;D2050&quot;.
      2.01 B. 8:  Revised to require emergency power for 50 percent of the lighting in electrical and mechanical rooms, eliminating discrepancy with the requirement of Element D5090 2.04, 24.  Revised to require emergency power for 100 percent of the lighting in telecommunications equipment rooms, eliminating discrepancy with the requirement of Element D501001 2.01 C.
      4.01 A:  Changed &quot;Z2050&quot; to &quot;D2050&quot;. 
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r06/D5020-M.pdf</link>
    <guid isPermaLink="false">D5020 ODG061412</guid>
    <pubDate>Thu, 14 Jun 2012 08:23:30 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 73 - Protective Relay and Device Coordination - MS051712</title>
    <description>
      Added the requirement, &quot;Arch Flash Hazard Analysis shall be provided per the requirements of applicable edition of NFPA 70E.&quot;, to paragraph 3.01 C.  
      Added distribution boards to the requirements within paragraphs 3.01 D &amp; E. - Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2073.doc</link>
    <guid isPermaLink="false">26 05 73 MS051712</guid>
    <pubDate>Thu, 17 May 2012 08:26:26 CDT</pubDate>
  </item>

  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG051712</title>
    <description>
      Added Coordination Study and Arc Flash Hazard Analysis requirement paragraph 3.01 C. 
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r07/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG051712</guid>
    <pubDate>Thu, 17 May 2012 08:26:21 CDT</pubDate>
  </item>

  <item>
    <title>Element D500001 - Electrical Renovation General  Design Guidelines - ODG051712</title>
    <description>
      Added 3.01 L. for the requirements of Coordination Study and Arc Flash Hazard Analysis.
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D500001-M.pdf</link>
    <guid isPermaLink="false">D500001 ODG051712</guid>
    <pubDate>Thu, 17 May 2012 08:26:20 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS050112</title>
    <description>
      Paragraph 2.03 - Deleted the requirement of &quot;solid&quot; conductor. Added requirement that cable and wire (all sizes) shall be stranded.
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
    <guid isPermaLink="false">26 05 19 MS050112</guid>
    <pubDate>Tue, 01 May 2012 08:24:11 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Cable Trays, and Boxes - MS050112</title>
    <description>
      Editorial corrections to 1.03 Reference Standards.

      Added 3.03 D. 5. To require, &quot;5.  PVC Coated Rigid Steel Conduit:
      a. PVC coated rigid steel conduit may be direct burial for underground installation when concrete encasement is not required.
      b. The PVC coated conduit shall be hot dip galvanized inside and out.  The PVC coated conduit factory-cut threads shall be protected with hot galvanized threads and a clear urethane coating.  Thread protectors shall be used on the exposed threads of the PVC coated conduit.  The PVC coating must have been investigated by UL as providing the primary corrosion protection for the rigid galvanized steel conduit.  The PVC coated rigid galvanized steel conduit must be certified and authorized to wear the ETL Verification Mark.
      c. Ferrous fittings for general service locations must be UL Listed with PVC as the primary corrosion protection.
      d. A PVC sealing sleeve extending one pipe diameter or two inches, whichever is less, shall be formed at every female fitting opening, except unions.  The inside sealing sleeve diameter shall be matched to the outside diameter of the conduit.&quot;

      Added 3.02 O to require, &quot;The support means for conduit installation, whether threaded rods, trapeze or other system, shall not be shared with non-electrical system.  Any deviation from this standard due to space constrain shall be submitted to the Owner.  Owner’s review does not necessarily guarantee an approval; therefore the Contractor is advised not to start installation prior to final approval.&quot;
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS050112</guid>
    <pubDate>Tue, 01 May 2012 08:24:10 CDT</pubDate>
  </item>   
  
  <item>
    <title>CSI Division 11 - Equipment, Section 11 53 13 - Chemical Fume Hoods and Biological Safety Cabinets - MS032712</title>
    <description>
      Added the following sentence: &quot;Lamps shall be 32w T8, medium bi-pin, 85CRI, electronic ballast, instant start.&quot; to paragraphs 2.05 P., 2.06 Q. and 2.07 R.
      Please direct Questions and Comments to David Cole at 713-745-0584.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div11/11%2053%2013.doc</link>
    <guid isPermaLink="false">11 53 13 MS032712</guid>
    <pubDate>Tue, 27 Mar 2012 08:25:32 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Cable Trays, and Boxes - MS011912</title>
    <description>
      Revised 3.02 D. 4. c. to read as, &quot;All underground conduits that are not encased in concrete and that are buried 18 inches or more below grade shall have their location identified by a warning tape that in placed in the trench at least 12 inches above the underground installation.&quot;
      Added 3.02 D. 4. d. to require, &quot;Warning tape. Underground cable and conduit detectable marking tape shall be 6 inches wide, red with black letters, imprinted with &quot;CAUTION – BURRIED ELECTRIC CABLE BELOW&quot; or similar. Tape shall be installed a minimum of 12 inches above the underground installation, and not more than 12 inches below finished grade.  Warning tape shall be visible at the point where the conduit emerges above ground at the service stubs.  Where fiber optic cable is to be installed in the conduit, an underground cable marking tape with a metallic detection strip shall be imprinted with &quot;CAUTION – BURRIED FIBER OPTIC CABLE BELOW&quot; or similar. Splicing of the tape shall be accomplished with metal clips to maintain electrical continuity along the length of the tape. Splices shall be wrapped with a waterproof adhesive tape.&quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS011912</guid>
    <pubDate>Thu, 19 Jan 2012 08:44:16 CDT</pubDate>
  </item>
  <!-- 
  <item>
    <title>CSI Division 26 - Electrical, Section 26 41 00 - Lightning Protection System - MS112211</title>
    <description>
      Deleted &quot;provide copper down conductors with bimetal transition at the roof assembly rated for the application&quot; from 2.01. I.  Added the requirement of &quot;Stranded or braided aluminum conductors shall be used on roofs that utilize aluminum components.  Aluminum conductors shall be immediately transitioned to copper conductors by using appropriate bimetal connectors, as soon as they depart from aluminum surfaces&quot; to 2.02. A. - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2041%2000.doc</link>
    <guid isPermaLink="false">26 41 00 MS112211</guid>
    <pubDate>Tue, 22 Nov 2011 08:40:24 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS092911</title>
    <description>
      Editorial correction.	 Paragraph 2.02 D. 4.
      Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS092911</guid>
    <pubDate>Thu, 29 Sep 2011 08:33:14 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 14 - Conveying Equipment, Section 14 21 00 - Electric Traction Elevators - MS092911</title>
    <description>
      Added putty pads to address electrical boxes exceeding 16 square inches. Paragraph 2.09 A.2.
      Please direct Question and Comments to Rodney Beseda at 713-792-2568.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div14/14%2021%2000.doc</link>
    <guid isPermaLink="false">14 21 00 MS092911</guid>
    <pubDate>Thu, 29 Sep 2011 08:31:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS082511</title>
    <description>
      Added new requirements for Industrial Control Panels per AFCO request, to cover the scope that is not currently covered by Integrated Automation System and the construction and wiring of the control panels that are not covered by BAS spec. Paragraph 2.03.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS082511</guid>
    <pubDate>Thu, 25 Aug 2011 08:22:26 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Cable Trays, and Boxes - MS082511</title>
    <description>
      Revised the minimum requirement of conduit size from 3/4&quot; to 1/2&quot; for cost saving. Added new requirement to 3.02 D. 1. that &quot;½-inch EMT may only be used for connections between distribution J-boxes in the ceiling and J-boxes in the walls within the same room, serving 15-20 Amp single phase receptacles, lighting occupancy sensors, switches, dimmers, and fire alarm respectively. In such application the length of ½-inch EMT shall not exceed 25 feet.&quot;.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS082511</guid>
    <pubDate>Thu, 25 Aug 2011 08:22:25 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Cable Trays, and Boxes - MS071911</title>
    <description>
      Revised the section title to read as, &quot;Raceways, Cable Trays, and Boxes&quot;. Revised the first two sentences of 3.01 D. to read as, &quot;Where raceways or cable trays penetrate fire-rated floors or roofs, sleeve and seal opening around raceways and cable trays with UL listed firestop assemblies equal to fire rating of floors or roofs. Seal penetrations through all floors or roofs to provide and maintain a watertight installation.&quot; Deleted 3.01 F., where it requires sleeve for fire rated wall penetration.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS071911</guid>
    <pubDate>Tue, 19 Jul 2011 08:38:14 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS060211</title>
    <description>
      Deleted the requirement in 2.02 B. that &quot;Hospital and patient care occupancies with three essential branches on emergency generator shall utilize yellow (life safety), blue (critical), and green (equipment) colors for nameplates. Yellow nameplates shall have black lettering. &quot; 
      Revised the requirement of 2.02 G. 3 that Fire alarm circuits (only) shall be marked with half red covers and &quot;Fire Alarm&quot; marked on the face of J-box.
      Revised 3.03 A. 2. to read as &quot;Testing shall be performed by an independent testing company that is Owner-approved, and National Electrical Testing Association (NETA) certified.&quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:14 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS060211</title>
    <description>
      Added 3.02 E. 4 to require, &quot;Conductors installed outdoors or in garages, whether in use or spare, shall be terminated in boxes that are rated for outdoor use with listed connectors that are rated for watertight/rain tight applications. The use of indoor wire nuts with electrical tape is prohibited for installations outdoors or in garages.&quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
    <guid isPermaLink="false">26 05 19 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:13 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS060211</title>
    <description>
      Added to and revised 3.02 E. 1 to require, &quot;Install all conduits parallel to or at 90 degrees to the structure. Multiple conduits shall not be installed using a single rod support. Multiple conduits running the same direction with spacing 48 inches apart or less shall be installed on the same trapeze. Conduits shall be installed on metal framing constructed trapeze hangers that have minimum 24-inch width. Trapeze hangers shall be supported on minimum 3/8-inch diameter all-thread rod attached to the structure with coupling nuts and expansion bolts or beam clamps. Conduit straps or other devices specifically designed for the purpose shall be used to secure conduits to the metal framing.  Wire ties and hanger wires are not permitted.  Conduits shall only be installed on the top surface of the metal framing, with multiple layered trapeze supports if required. Hanger rods shall not extend more than 1 inch pass the lower trapeze metal framing. &quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 13 00 - Medium-Voltage Switchgear - MS060211</title>
    <description>
      Changed the format of 1.03 C.  References, corrected some of the titles and added the requirement of &quot;UL 1449 – Standard for Safety for Surge Protective Devices, 3rd Edition&quot;.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2013%2000.doc</link>
    <guid isPermaLink="false">26 13 00 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:11 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 23 00 - Low Voltage Switchgear - MS060211</title>
    <description>
      Corrected some of the titles of 1.03 C. References, and added the requirement of &quot;UL 1449 – Standard for Safety for Surge Protective Devices, 3rd Edition&quot;.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2023%2000.doc</link>
    <guid isPermaLink="false">26 23 00 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 43 13 - Transient Voltage Surge Suppressors - MS060211</title>
    <description>
      Corrected some of the references titles in paragraphs 1.03 C., 1.03 D., 1.04 A. 1., 1.04 B. 2, and 1.04 B. 3.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2043%2013.doc</link>
    <guid isPermaLink="false">26 43 13 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:09 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 51 00 - Lighting Fixtures - MS060211</title>
    <description>
      Revised 2.07 A. to read as &quot;Incandescent lamps shall not be used.&quot; Revised 2.07 B. to read as &quot;Pin-based compact fluorescent lamps shall be quad or triple tube, 13, 18, 26 or 32 watt similar to NEMA lamp type CFQ13W/G24Q/835 or CFTR26W/GX24Q/835. Long compact fluorescent lamps in nominal 39 and 40 watt sizes are acceptable. Compact fluorescent lamps shall be 3500K color temperature. Original equipment manufacturer lamps that are only available from a single manufacturer are not acceptable.&quot;  Revised 2.07 C to read as &quot;Linear fluorescent rapid, or instant-start lamps shall be medium bi-pin equal to or better than Philips T-8 lamps, minimum CRI of 85. General use four foot lamps shall be equal to or better than Philips Energy Advantage F32T8/ADV841/XEW/ALTO.  If different lamp manufacturers are submitted, no noticeable difference in color temperature shall be allowed and performance shall be equal to or better than the base lamp. T-8 fluorescent lamps shall have a color temperature of 4100 K and be specified in 2 foot, 3 foot and 4 foot lengths only. U-bent (6 inch, 3 inch, 1-5/8 inch) and circline lamps are not acceptable. Linear four foot lamps used in open fixtures in environments below 70 degrees F, or in operation rooms, shall be full wattage type.&quot;  Revised 2.07 D. to read as "D. Metal halide HID lamps shall be ceramic metal halide type, clear, unless noted otherwise, with mogul or medium bases. Acceptable medium base lamp sizes are 50, 100 and 150 watts. Double-ended lamps are not acceptable.  Any base type other than medium or mogul shall be submitted for Owner review and approval in advance. Metal halide fixtures shall be lensed or utilize a lamp (PAR type) which does not require special arc tube protection.&quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2051%2000.doc</link>
    <guid isPermaLink="false">26 51 00 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:29:08 CDT</pubDate>
  </item> 
  
  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG031711</title>
    <description>
      Added requirement to 2.01 F. 10: &quot;Distribution equipment such as switchgears, switchboards, panelboards, and distribution boards shall be housed in dedicated electrical rooms. Electrical rooms shall be designed in such a way that meets NEC requirements of working space, headroom, dedicated spaces above electrical equipment, entrance and exit doors. The size of dedicated electrical rooms shall accommodate the initial installation of core and shell as well as anticipated final installation of build-outs.&quot;  Deleted the reference of motor control center in 2.02 F12. Clarified that 1-hour fire rating for electrical rooms with &quot;dry-type transformers of more than 112½ kVA rating.&quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r06/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:26:18 CDT</pubDate>
  </item>

  <item>
    <title>Element D5022 - Master Lighting Fixture Schedule - ODG031711</title>
    <description>
      Clarified that A/E shall incorporate &quot;at least three equivalent or better manufacturers&quot; for project lighting fixture schedule.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r05/D5022-M.pdf</link>
    <guid isPermaLink="false">D5022 ODG031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:26:16 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways Conduits and Boxes - MS030311</title>
    <description>
      Added requirement to paragraph 2.08 B. 2, &quot;Surface metal raceways installed in controlled environmental and cold rooms.  Install gasket flip type weather resistant cover plates in lieu of stainless cover plates for receptacles.&quot; - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS030311</guid>
    <pubDate>Thu, 03 Mar 2011 08:33:18 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 24 16 - Panelboards - MS030311</title>
    <description>Added requirement to paragraph 3.01. J, &quot;Hardware for connections to interior terminals and breakers shall be installed and torqued per manufacturer’s published recommendations by hand tools.  Electric or cordless drills/screwdrivers, which are suspected to be the main cause of the stripped out threads in the screw holes for terminal bars and bolt-on breakers, therefore are prohibited&quot; and &quot;The use of prohibited tools observed and/or evidence of damaged parts regardless of the cause are subject to rejection and removal from the project immediately per the direction of Owner’s representative.&quot; - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2024%2016.doc</link>
    <guid isPermaLink="false">26 24 16 MS030311</guid>
    <pubDate>Thu, 03 Mar 2011 08:33:16 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 51 00 - Lighting Fixtures - MS030311</title>
    <description>Added requirement to paragraph 3.01 I. 1, &quot;MC (Metal-Clad Cable) and FMC (Flexible Metal Conduit), where are permitted to be used, shall be concealed to prevent physical damage.  Exposed MC and FMC installations are not acceptable.&quot; - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2051%2000.doc</link>
    <guid isPermaLink="false">26 51 00 MS030311</guid>
    <pubDate>Thu, 03 Mar 2011 08:33:14 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS021711</title>
    <description>Delete the sentences of &quot;Only lighting circuits may share grounding conductors. All lighting circuits with shared grounding conductors shall be number 10 AWG minimum&quot;. Paragraph 3.02 C. 4. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
    <guid isPermaLink="false">26 05 19 MS021711</guid>
    <pubDate>Thu, 17 Feb 2011 08:34:15 CDT</pubDate>
  </item>
  
  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG112310</title>
    <description>
      Added requirement of &quot;Consideration should be given to the physical separation of the main feeders of the emergency electrical system from the normal wiring of the facility to prevent possible simultaneous destruction as a result of a local catastrophe&quot; to G. 1.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r05/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG112310</guid>
    <pubDate>Tue, 23 Nov 2010 08:45:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 41 00 - Lightning Protection System - MS093010</title>
    <description>
      Added requirement to 1.05 A. - &quot;Alternate installation detail for rooftop lightning terminals shall be developed if the attachment to parapet wall is prohibited due to the concern of roof warranty.&quot; - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2041%2000.doc</link>
    <guid isPermaLink="false">26 41 00 MS093010</guid>
    <pubDate>Thu, 30 Sep 2010 08:32:18 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 20 - Common Fire Suppression, Plumbing and HVAC Requirements, Section 20 05 13 - Motors - MS093010</title>
    <description>
      Added requirement to 3.03 C. - &quot;Motor phase loss and phase unbalance protection shall be tested.&quot; - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div20/20%2005%2013.doc</link>
    <guid isPermaLink="false">20 05 13 MS093010</guid>
    <pubDate>Thu, 30 Sep 2010 08:32:16 CDT</pubDate>
  </item>

  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG091610</title>
    <description>
      Added requirement to 2.01 U. 8 – All receptacles in elevator equipment room shall be GFCI type. 
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r04/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG091610</guid>
    <pubDate>Thu, 16 Sep 2010 08:35:11 CDT</pubDate>
  </item>

  <item>
    <title>Element D5020 - Lighting and Branch Wiring - ODG091610</title>
    <description>
      Added requirement to 2.01 B. 8 – Do not use occupancy sensor for lighting control in elevator equipment room, provide single pole lighting switch.
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r05/D5020-M.pdf</link>
    <guid isPermaLink="false">D5020 ODG091610</guid>
    <pubDate>Thu, 16 Sep 2010 08:35:09 CDT</pubDate>
  </item>

  <item>
    <title>Element D5022 - Master Lighting Fixture Schedule - ODG091610</title>
    <description>
      Revised 1.01 Overview to read as:
      A.	The following Table lists lighting fixture types, manufacturers, and models that are based on various applications at MD Anderson facilities.
      B.	The A/E shall use the following baseline lighting fixture schedule in developing a project specific lighting fixture schedule.  The A/E shall incorporate at least (1) additional equivalent manufacturer(s) and associated catalog numbers per each type of fixture.  The criterion for evaluation of equivalency shall include, but not limited to, photometric characteristic, material, construction, features, finishes, lenses, and cost, etc.
      C.	Other manufacturers for lighting fixture(s) or lamp(s) equal (or better than) in design, performance and function will be consid¬ered upon AE’s evaluation and approval. The approved lighting fixture(s) or lamp(s) shall be incorporated into project specific lighting fixture schedule.
      D.	Substitution to approved project lighting fixture schedule shall follow the substitution procedure outlined in 01 31 00 - Project Administration.
      Added alternate manufacturers to type FA, FF, FF1, FG, FG1 lighting fixtures.
      Added manufacturers for LED lighting fixtures.
      Revised Note 5 to read as: &quot;All linear fluorescent lamps shall contain no more than 1.7 mg mercury.  All four foot linear lamps shall be high efficiency equivalent to or better than Philips F32T8/ADV841/XEW/ALTO2 or Sylvania FO32/25W/8410XP/SS/ECO 25 watt lamps.&quot;
      Added Note 6: &quot;Provide program start ballast where occupancy sensor is being specified.&quot;
      Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r04/D5022-M.pdf</link>
    <guid isPermaLink="false">D5022 ODG091610</guid>
    <pubDate>Thu, 16 Sep 2010 08:35:07 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 36 24 - 5kV Automatic Transfer Switches - MS081710</title>
    <description>
      Initial issue of Section. - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2036%2024.doc</link>
    <guid isPermaLink="false">26 36 24 MS081710</guid>
    <pubDate>Tue, 17 Aug 2010 08:49:11 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 36 25 - 5kV Emergency Generator Paralleling Switchgear - MS081710</title>
    <description>
      Initial issue of Section. - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2036%2025.doc</link>
    <guid isPermaLink="false">26 36 25 MS081710</guid>
    <pubDate>Tue, 17 Aug 2010 08:49:09 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS081210</title>
    <description>
      Added statement, &quot;Temporary power equipment and distribution for construction shall not occupy building spaces or block pathways that are designated for permanent installation of other trades according to design drawings.&quot; Paragraph 3.02 O. - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS081210</guid>
    <pubDate>Thu, 12 Aug 2010 08:39:12 CDT</pubDate>
  </item> 
  
  <item>
    <title>Element D501001 - Electrical System for Telecommunications Rooms - ODG072910</title>
    <description>
      Initial Adoption and Posting of Element.
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r00/D501001-M.pdf</link>
    <guid isPermaLink="false">D501001 ODG072910</guid>
    <pubDate>Thu, 29 Jul 2010 08:53:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways Conduits and Boxes - MS072210</title>
    <description>
      Added 1.05 B. 3. clarifying submittal requirements for firestopping installation Shop Drawing.
      Revised 3.01 D. to read as, &quot;Where raceways penetrate fire-rated floors, sleeve and seal opening around raceway with UL listed firestop equal to fire rating of floor.  Seal penetrations through all floors to provide and maintain a watertight installation.  Conduit sleeves, where required, shall be two (2) trade sizes larger for proper sealing and extend 2 inches above the surface.  Refer to Section 07 84 13 Penetration Firestopping and Section 09 29 00 Gypsum Drywall for sealing and firestopping requirements where raceways penetrate smoke, fire, and sound rated walls.  The installation shall be in compliance with UL listed firestopping assembly.&quot;
      Revised 3.04 D. to read as, &quot;Avoid installing boxes back-to-back in walls by providing minimum 6-inch separation in non-fire-rated walls.  Provide minimum 24-inch horizontal separation in acoustic-rated walls.  Where walls or partitions are required to have a maximum 2-hour fire rating, recessed steel electrical boxes shall not exceed 16 square inches in area, provided the aggregate area of the openings does not exceed 100 square inches in any 100 square feet of wall area.  The annular space between the wall membrane and the box shall not exceed 1/8 inch.  Such boxes on opposite sides of the wall or partition shall be either separated by a horizontal distance of not less than 24 inches or separated by protecting both boxes by listed putty pads.&quot; - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:33:24 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 32 13 - Packaged Engine Generator Systems - MS072210</title>
    <description>
      Added code requirement of &quot;NFPA 101 – Life Safety Code&quot; to 1.03 C.  Added 2.07 A. to address NFPA 101 requirement of remote generator annunciator in Fire Command Room. - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2032%2013.doc</link>
    <guid isPermaLink="false">26 32 13 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:33:22 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 36 23 - Automatic Transfer Switches - MS072210</title>
    <description>
      Added requirmenet of &quot;Products or similar model in design that is known for causing incident in MD Anderson facilities within the past eight years shall not be selected&quot; to 2.01 A.  Revised 2.02 B. 1. to read as &quot;ASCO&quot;.  Revised 2.04 P. to read as &quot;Provide an elevator pre-signal before transfer to Normal after operating on Emergency during an outage.  Provide pre-signal for testing, and for switching during transfer between energized sources.&quot; - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2036%2023.doc</link>
    <guid isPermaLink="false">26 36 23 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:33:20 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 41 00 - Lightning Protection System - MS072210</title>
    <description>
      Added requirement of &quot;Provide intermediate-level potential equalization for reinforced concrete structure buildings, interconnecting the lightning protection system down conductors and other grounded media with a loop conductor at intermediate levels not exceeding 200 ft per NFPA 780.&quot; Paragraph 1.05 E. - Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2041%2000.doc</link>
    <guid isPermaLink="false">26 41 00 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:33:18 CDT</pubDate>
  </item>

  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG070810</title>
    <description>
      Added new paragraphs of 2.01 F. Normal Power Distribution 1, 2, and 3.  Added new paragraph G. Emergency Power Distribution (including G. 1. through G. 7.)  Added the requirement of &quot;Do not mount panelboards in fire rated walls&quot; to 2.01 I.  Revised 2.01 J. to read as &quot;Do not design floor slab encased conduit runs for the branch circuitry except slab on grade.  The other exception may be for the lighting grid in the parking deck areas of a parking garage.&quot;  Added new paragraphs R, S, and T.  Deleted 2.01 W. of &quot;provide power on the roof for building cleaning equipment&quot;, since this is redundantly stated in 2.01 U. 2 and 3.  Added requirement of &quot;arc flash&quot; to 3.01 B. Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:45:54 CDT</pubDate>
  </item> 
  
  <item>
    <title>Element D5020 - Lighting and Branch Wiring - ODG070810</title>
    <description>
      Revised 4.01 D. to read as &quot;Do not specify 8-foot fluorescent lamps, or T-12 lamps of any length.&quot;  Revised 4.01 F. to read as &quot;Exit signs shall be LED type.&quot; Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r04/D5020-M.pdf</link>
    <guid isPermaLink="false">D5020 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:45:52 CDT</pubDate>
  </item>

  <item>
    <title>Element D5090 - Other Electrical Systems - ODG070810</title>
    <description>
      Added 2.11 B. requiring &quot;Provide intermediate-level potential equalization for reinforced concrete structure building, interconnecting the lightning protection system down conductors and other grounded media with a loop conductor at intermediate levels not exceeding 200 ft per NFPA 780.&quot;  Please direct Question or Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D5090-M.pdf</link>
    <guid isPermaLink="false">D5090 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:45:50 CDT</pubDate>
  </item> 
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 73 - Protective Relay and Device Coordination - MS052710</title>
    <description>
      Added requirement to submit sample of Arc Flash warning label. Paragraph 1.04 C.
      Included requirement of arc flash hazard label pertaining to specific warnings, color, equipment designation, size, and etc. Paragraph 2.01. - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2073.doc</link>
    <guid isPermaLink="false">26 05 73 MS052710</guid>
    <pubDate>Thu, 27 May 2010 08:46:22 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 14 - Conveying Equipment, Section 14 21 00 - Electric Traction Elevators - MS030910</title>
    <description>2.02 A: added requirement that manufacturer's models must be in service minimum 5-years; 2.03 B.7.f: added requirement for isolation transformers. - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div14/14%2021%2000.doc</link>
    <guid isPermaLink="false">14 21 00 MS030910</guid>
    <pubDate>Tue, 09 Mar 2010 08:12:19 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 14 - Conveying Equipment, Section 14 21 00 - Electric Traction Elevators - MS030410</title>
    <description>Added phase protection requirement for drive system. Paragraph 2.03 B.7.c. - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div14/14%2021%2000.doc</link>
    <guid isPermaLink="false">14 21 00 MS030410</guid>
    <pubDate>Thu, 04 Mar 2010 08:22:16 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS030410</title>
    <description>Added requirement of &quot;All unused openings such as but not limited to, knockouts on panels and boxes, surface wireway openings, busway openings, circuit breaker empty slots shall be covered with approved cover plates.&quot; Paragraph 2.02 N. - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS030410</guid>
    <pubDate>Thu, 04 Mar 2010 08:22:14 CDT</pubDate>
  </item>
  
  <item>
    <title>Element D5010 - Electrical Service and Distribution - ODG030210</title>
    <description>
      2.01 F. 4. a. - Revised the minimum bus size for 277 lighting panel to 125A.  2.01 F. 7. - Revised the term of &quot;transient voltage surge suppression&quot; to &quot;surge arrester&quot; for substations and main switchboard.  2.01 F. 9. - Added requirement of &quot;provided phase shift calculation and projected harmonic cancellation&quot;.
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D5010-M.pdf</link>
    <guid isPermaLink="false">D5010 ODG030210</guid>
    <pubDate>Tue, 02 Mar 2010 08:16:44 CDT</pubDate>
  </item>
  
  <item>
    <title>Element D5020 - Lighting and Branch Wiring - ODG030210</title>
    <description>
      2.01B. 4. - Eliminated incandescent lamps.  2.01 H. 1 - Added the requirement of &quot;provide with wire guard where subject to physical damage&quot;.  2.01 I. 2. - Revised the ASHRAE 90.1 reference to 9.4.5.  4.01 B. - Added the requirement of &quot;four foot T8 lamps shall be 25 watt high efficiency type with mercury content of 1.7 mg or less&quot;.  4.01 I. - Added the requirement of &quot;two, three and four foot lamps shall be with mercury content of 1.7 mg or less&quot;.
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D5020-M.pdf</link>
    <guid isPermaLink="false">D5020 ODG030210</guid>
    <pubDate>Tue, 02 Mar 2010 08:16:42 CDT</pubDate>
  </item>

  <item>
    <title>Element D5022 - Master Lighting Fixture Schedule - ODG030210</title>
    <description>
      Revisions made to type FA, FB, FC, FD, FE, FF, FF1, FG, FG1, FN, FO, FP, FT, M1, fixtures. Deleted Phoenix DL70MHDWT60-277, and Widelight RSPM-100-RSPM-100-S-277-LMP-PND-RC-F1-SA,  Added Speclight FSW4332S2X20 AR MVOLT TUBIHP STSL, and Prudential WAL-8-SD-2T8-04-YGW-SC-277-WM-DM.
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r04/D5022-M.pdf</link>
    <guid isPermaLink="false">D5022 ODG030210</guid>
    <pubDate>Tue, 02 Mar 2010 08:16:40 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 13 - Cable and Terminations (Medium Voltage) - MS021110</title>
    <description>Clarified the method of identifying cables by &quot;brass tags embossed in letters no less than one-half inch high, permanently&quot; affixed to &quot;each current carrying cable&quot;. Paragraph 3.02 D. 1.	- Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2013.doc</link>
    <guid isPermaLink="false">26 05 13 MS021110</guid>
    <pubDate>Thu, 11 Feb 2010 08:17:29 CDT</pubDate>
  </item>
  
  <item>
    <title>Element D5037 - Fire Alarm and Smoke Detector Systems - ODG020410</title>
    <description>
      Initial Adoption of Element. 
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r00/D5037-M.pdf</link>
    <guid isPermaLink="false">D5037 ODG020410</guid>
    <pubDate>Thu, 04 Feb 2010 08:35:19 CDT</pubDate>
  </item>
  
  <item>
    <title>Element Z2005 - Codes and Applicable Regulatory Agencies - ODG122209</title>
    <description>
      Paragraph 2.04 A. 6. – Added reference to the 2009 Edition of the Standard for Electrical Safety in the Workplace, NFPA 70E
      Please direct Questions and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/Z2005-M.pdf</link>
    <guid isPermaLink="false">Z2005 ODG122209</guid>
    <pubDate>Tue, 22 Dec 2009 08:07:24 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 24 16 - Panelboards - MS122209</title>
    <description>Made editorial corrections to titles of various referenced standards. Paragraph 1.03 C. - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2024%2016.doc</link>
    <guid isPermaLink="false">26 24 16 MS122209</guid>
    <pubDate>Tue, 22 Dec 2009 08:07:22 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS120109</title>
    <description>Deleted general requirement of sleeve for conduit penetrating fire rated wall. Revised to read as &quot;Refer to Divisions 07 and 09 for sealing and firestopping requirements where raceways penetrate smoke, fire, and sound rated walls.&quot; Paragraph 3.01 D. - Please direct Question or Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2001%2000.doc</link>
    <guid isPermaLink="false">26 01 00 MS120109</guid>
    <pubDate>Tue, 01 Dec 2009 08:06:12 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS120109</title>
    <description>Deleted general requirement of sleeve for conduit penetrating fire rated wall. Revised to read as &quot;Refer to Divisions 07 and 09 for sealing and firestopping requirements where raceways penetrate smoke, fire, and sound rated walls.&quot;	Paragraph 4.02 M. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS120109</guid>
    <pubDate>Tue, 01 Dec 2009 08:06:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS102209</title>
    <description>Allowed branch circuit #10 AWG and smaller to be solid copper.  Allowed lighting circuits with shared grounding conductor not to have tracer colors on the wire.  Allowed lighting circuits sharing grounding conductors and the shared grounding conductors shall be #10 AWG minimum. Paragraphs 2.03 C., 2.03 E. 2., 3.02 C. 4. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
    <guid isPermaLink="false">26 05 19 MS102209</guid>
    <pubDate>Thu, 22 Oct 2009 07:34:25 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS102209</title>
    <description>Required single conduit installation to be &quot;suspended from all thread rods, conduit clamps with bolts and nuts shall be used&quot;.  Banned clip type conduit fastener. Paragraph 3.02 F. 1. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
    <guid isPermaLink="false">26 05 33 MS102209</guid>
    <pubDate>Thu, 22 Oct 2009 07:34:27 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 26 - Electrical, Section 26 25 13 - Low Voltage Busways - MS102209</title>
    <description>Initial Issue of Section. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2025%2013.doc</link>
    <guid isPermaLink="false">26 25 13 MS102209</guid>
    <pubDate>Thu, 22 Oct 2009 07:34:29 CDT</pubDate>
  </item>  
     
<item>
<title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS080609</title>
<description>Added the requirements of &quot;Provide raceway support in intervals not exceeding the maximum spacing per NEC&quot; and &quot;Through partition wall penetration shall not be construed as a means of conduit support.&quot; Paragraphs 3.01 I. and 3.02 F. 1. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
<guid isPermaLink="false">26 05 33 MS080609</guid>
<pubDate>Thu, 06 Aug 2009 07:24:19 CDT</pubDate>
</item>

<item>
<title>Electrical Design Guideline Element D5090 - Other Electrical Systems - ODG080609</title>
<description>Added verbiage to identify lab systems that need to be fed from emergency power, and to define demand factors of emergency power for various systems in sizing generator per John Pham. Paragraph 2.01 D. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D5090-M.pdf</link>
<guid isPermaLink="false">D5090 ODG080609</guid>
<pubDate>Thu, 06 Aug 2009 07:24:12 CDT</pubDate>
</item>


<item>
<title>CSI Division 26 - Electrical, Section 26 09 13	- Power Status and Monitoring System - MS072309</title>
<description>Revised and replaced the old computer reference of &quot;Windows 2000&quot; and &quot;floppy disk&quot; by &quot;Windows Server 2008&quot; and &quot;compact disc&quot;.  Made editorial corrections.	Paragraphs 2.08 A.1.a. and 2.08 F.2. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2009%2013.doc</link>
<guid isPermaLink="false">26 09 33 MS072309</guid>
<pubDate>Thu, 23 Jul 2009 07:22:06 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS070209</title>
<description>Deleted requirement of expansion fittings for conduit straight runs in excess of 100 feet.  Added requirement that J-boxes be provided for branch circuits in excess of 100 feet. Minor editorial changes.	Paragraphs 3.02 H. 2., 3.04 - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
<guid isPermaLink="false">26 05 33 MS070209</guid>
<pubDate>Thu, 02 Jul 2009 07:19:06 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS063009</title>
<description>Changed &quot;mechanical damage&quot; to &quot;physical damage&quot;. Added &quot;Raceway system run on surface of finished floor is unacceptable.&quot; Paragraphs 3.02 D. 1. and 3.02 I. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
<guid isPermaLink="false">26 05 33 MS063009</guid>
<pubDate>Tue, 30 Jun 2009 08:15:09 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 22 13 - Non-K Factor Dry-Type Transformers - MS051409</title>
<description>Added new requirement, &quot;All-thread coupling shall not be used on hanger rod shorter than 10 feet.  The quantity of all-thread coupling, where used, shall not exceed more than one in a 10-foot section.  All-thread coupling shall be backed by a ½-inch nut, which is tightened, at each end of the coupling.&quot; Paragraph 3.01 E. - Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2022%2013.doc</link>
<guid isPermaLink="false">26 22 13 MS051409</guid>
<pubDate>Thu, 14 May 2009 07:11:16 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS040209</title>
<description>Deleted manufacturers Capital, Diamond Wire, Rome, and Triangle PWC.  Added Encore. Paragraph 2.02. - Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
<guid isPermaLink="false">26 05 19 MS040209</guid>
<pubDate>Thu, 02 Apr 2009 07:16:52 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 73 - Protective Relay and Device Coordination - MS040209</title>
<description>Additional requirement of electronic copy of electrical system analysis in SKM format.  The electronic copy of Short-Circuit/Coordination Study/Arc Flash Hazard Analysis shall be demonstrated and validated to the Owner, on Contractor’s computer where SKM software is installed.  Clarified that Arc flash hazard warning signs and labels shall be factory affixed to electrical distribution equipment, in compliance with NFPA 70E, by the equipment manufacturer. Paragraphs 3.01 G. and 3.01 H. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2073.doc</link>
<guid isPermaLink="false">26 05 73 MS040209</guid>
<pubDate>Thu, 02 Apr 2009 07:16:42 CDT</pubDate>
</item>

  <item>
    <title>Installation Details for CSI Division 26 - Electrical - ee101509</title>
    <description>
       Various details; EE-260526-01, EE-260533-01 through 09. - Please direct Question and Comments to James Da at 713-745-5729.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/details.html</link>
    <guid isPermaLink="false">Details ee101509</guid>
    <pubDate>Thu, 15 Oct 2009 07:50:12 CDT</pubDate>
  </item>  
  
<item>
<title>Electrical Design Guideline Element D5000 - Load Calculation Criteria - ODG022409</title>
<description>Deleted reference to the 2004 version of ASHRAE 90.1. The 2007 version was adopted by the State of Texas on January 01, 2009. Paragraphs 2.01 A. 1. and 3.01 B. 7. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D5000-M.pdf</link>
<guid isPermaLink="false">D5000 ODG022409</guid>
<pubDate>Tue, 24 Feb 2009 07:44:19 CDT</pubDate>
</item>

<item>
<title>Electrical Design Guideline Element D5020 - Lighting and Branch Wiring - ODG022409</title>
<description>Deleted reference to the 2004 version of ASHRAE 90.1. The 2007 version was adopted by the State of Texas on January 01, 2009. Paragraph 2.01 A. 1. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D5020-M.pdf</link>
<guid isPermaLink="false">D5020 ODG022409</guid>
<pubDate>Tue, 24 Feb 2009 07:44:18 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 35 33 - Power Factor Correction Equipment - MS021209</title>
<description>Initial Issue of Section. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2035%2033.doc</link>
<guid isPermaLink="false">26 35 33 MS021209</guid>
<pubDate>Thu, 12 Feb 2009 08:12:12 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS021209</title>
<description>Added &quot;Do not daisy chain conduit installations in or on walls, provide a single conduit wall drop per device.&quot; per Ray Cosgrove's request. Paragraph 3.03 N. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
<guid isPermaLink="false">26 05 33 MS021209</guid>
<pubDate>Thu, 12 Feb 2009 08:12:11 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 32 13 - Packaged Engine Generator Systems - MS011509</title>
<description>Included sustainability requirements based upon TGCE's evaluation, Paragraphs 2.05 A 7 and 2.05 K 1. - Please direct Questions and Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2032%2013.doc</link>
<guid isPermaLink="false">26 32 13 MS011509</guid>
<pubDate>Thu, 15 Jan 2009 07:14:22 CDT</pubDate>
</item>

<item>
<title>Electrical Design Guideline Elements D5000, D500001, D5010, D5020, D5022 and D5090 - ODG120908</title>
<description>Included sustainability requirements throughout document based upon the Tom Green and Company evaluation. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/Guides/Table%20of%20Contents-M.pdf</link>
<guid isPermaLink="false">Electrical Elements ODG120908</guid>
<pubDate>Tue, 09 Dec 2008 07:32:17 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 26 - Grounding - MS120408</title>
<description>Revised various requirements throughout the entire document. Refer to the Master Specification Revision Log located on the Owner's Design Guidekines web site for details of changes. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2026.doc</link>
<guid isPermaLink="false">26 05 26 MS120408</guid>
<pubDate>Thu, 04 Dec 2008 08:12:23 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 73 - Protective Relay and Device Coordination - MS111808</title>
<description>Add a note to specification editer,  &quot;For renovation projects, revise this sentence to read, This work is to be performed by the Engineer.&quot; Paragraph 1.02 B. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2073.doc</link>
<guid isPermaLink="false">26 05 73 MS111808</guid>
<pubDate>Tue, 18 Nov 2008 08:09:13 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 23 00 - Low Voltage Switchgear - MS111808</title>
<description>Revise original submittal requirement of  &quot;Coordination curve for each type and rating of circuit breaker&quot; to read as &quot;Coordination study for each type and rating of circuit breaker.&quot; Paragraph 1.04. A. 1. h. - Please direct Questions or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2023%2000.doc</link>
<guid isPermaLink="false">26 23 00 MS111808</guid>
<pubDate>Tue, 18 Nov 2008 08:09:12 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 13 - Cable and Terminations (Medium Voltage) - MS111308</title>
<description>Deleted Cablec Cable since it is no longer in business. Paragraph 2.02 A. 2. - Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2013.doc</link>
<guid isPermaLink="false">26 05 13 MS111308</guid>
<pubDate>Thu, 13 Nov 2008 08:12:13 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 19 - Cable, Wire and Connectors, 600 Volt - MS111308</title>
<description>Replaced standards reference of NEMA WC3 and NEMA WC5 by NEMA WC70. Paragraph 2.03 A. and B. - Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2019.doc</link>
<guid isPermaLink="false">26 05 19 MS111308</guid>
<pubDate>Thu, 13 Nov 2008 08:12:12 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 05 33 - Raceways, Conduits, and Boxes - MS111308</title>
<description>Revised requirement from &quot;No raceways, either metallic or non-metallic, flexible or rigid, shall be installed in any floor slab above slab on grade&quot; to &quot;No raceways, either metallic or non-metallic, flexible or rigid, shall be installed in any floor slab elevated above slab on grade&quot;. Paragraph 3.01 G. - Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div26/26%2005%2033.doc</link>
<guid isPermaLink="false">26 05 33 MS111308</guid>
<pubDate>Thu, 13 Nov 2008 08:12:11 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 41- 00 - Lightning Protection System - MS090208</title>
<description>Expanded specification to include system design, installation, grounding bonding and certification.  Listed cross reference specs of 26 01 00, 26 05 26, 26 05 33.  Added code references of NFPA 70, UL 96, UL 96A, NFPA  780, and LPI 175.  Manufacturer qualification to include three years documented experience.  Installer qualification to include minimum ten years documented experience.  Newly defined System Design.  Submittal to include product data showing dimensions and materials of each component, and included indication of listing in accordance with UL 96.  Additional requirements for shop drawings and as-built drawings.  Material compatibility requirement.  Conductor shall be stranded or braided.  Roof penetration fittings shall incorporate a positive means for sealing around the penetration.  Added requirement for ground ring electrode.  Added requirement for preparing surfaces to receive work.  Protect elements surrounding work of this Section from damage or disfiguration.  Concealed down conductors shall be installed in PVC.  Installer to request a final inspection by the Owner prior to concealment of components and connections. Paragraphs 1.02 A, 1.02 C, 1.03 A, 1.04, 1.05, 1.06, 2.01 I, 2.02, 2.06 A, 3.01 A, 3.01 C, 3.01 D, 3.02 C. 1, 3.02 G. 1. Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div26</link>
<guid isPermaLink="false">26 41 00 MS090208</guid>
<pubDate>Tue, 02 Sep 2008 09:19:14 CDT</pubDate>
</item>

<item>
<title>CSI Division 26 - Electrical, Section 26 01 00 - Basic Electrical Requirements - MS052208</title>
<description>Deleted - Contractor is ultimately responsible for its installation in compliance with NEC requirement pertaining to working space and dedicated equipment space regardless whether or not such space dimensions are indicated on drawings. Paragraph 3.02 A. - Please direct Question or Comments to James Da at 713-745-5729.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div26</link>
<guid isPermaLink="false">26 01 00 MS052208</guid>
<pubDate>Thu, 22 May 2008 09:23:19 CDT</pubDate>
</item>
-->
