    <title>Element D4000 - Fire Protection General Design Guidelines - ODG122012</title>
    <description>
      Added requirements for maintaining fire detection and protection systems for Project duration. Paragraphs 2.03 D - G. 
       Please direct Questions and Comments to Bryan Galloy at 713-792-1284.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D4000-M.pdf</link>
    <guid isPermaLink="false">D4000 ODG122012</guid>
    <pubDate>Thu, 20 Dec 2012 08:44:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 10 13 - Wet Standpipe and Sprinkler Systems - MS122012</title>
    <description>
      Substantial revisions throughout document. Incorporated renovation requirements within this section. Added the following to section title, &quot;For New Installations and Reconfigurationation or Expansion of Existing Systems&quot;.
      Please direct Questions and Comments to Bryan Galloy at 713-792-1284.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2010%2013.doc</link>
    <guid isPermaLink="false">21 10 13 MS122012</guid>
    <pubDate>Thu, 20 Dec 2012 08:44:09 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 10 14 - Wet Standpipe and Sprinkler Systems Renovation - MS122012</title>
    <description>
      Deleted and Archived Section.
      Please direct Questions and Comments to Bryan Galloy at 713-792-1284.
    </description>
    <link></link>
    <guid isPermaLink="false">21 10 14 MS122012</guid>
    <pubDate>Thu, 20 Dec 2012 08:44:08 CDT</pubDate>
  </item>
  <!-- 
  <item>
    <title>Element D4010 - Wet Standpipe and Sprinkler Systems - ODG120811</title>
    <description>
      2.01 J. 2. – Revised fire water break tank sizing criteria.
      2.01 N &amp; O – Clarified riser drain and PRV test discharge requirements.
      3.01 A. – Added requirement that drain discharge locations be identified on drawings.
      Please direct Questions and Comments to Bryan Galloy at 713-792-1284.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D4010-M.pdf</link>
    <guid isPermaLink="false">D4010 ODG120811</guid>
    <pubDate>Thu, 08 Dec 2011 08:33:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 10 13 - Wet Standpipe and Sprinkler Systems - MS120811</title>
    <description>
      Clarified riser drain and PRV test discharge requirements. Paragraph 3.01 G.
      Please direct Questions and Comments to Bryan Galloy at 713-792-1284.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2010%2013.doc</link>
    <guid isPermaLink="false">21 10 13 MS120811</guid>
    <pubDate>Thu, 08 Dec 2011 08:33:09 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 10 14 - Wet Standpipe and Sprinkler Systems Renovation - MS120811</title>
    <description>
      Clarified riser drain and PRV test discharge requirements. Paragraph 3.02 F.
      Please direct Questions and Comments to Bryan Galloy at 713-792-1284.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2010%2014.doc</link>
    <guid isPermaLink="false">21 10 14 MS120811</guid>
    <pubDate>Thu, 08 Dec 2011 08:33:08 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 13 16 - Preaction Sprinkler Systems - MS042611</title>
    <description>Initial Adoption and Posting of Section.
      Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2013%2016.doc</link>
    <guid isPermaLink="false">21 13 16 MS042611</guid>
    <pubDate>Tue, 26 Apr 2011 08:23:14 CDT</pubDate>
  </item>
    
  <item>
    <title>Element D4000 - Fire Protection General Design Guidelines - ODG070810</title>
    <description>
      Paragraph 2.01 E. – Replaced &quot;City of Houston&quot; with &quot;Municipality&quot;. Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D4000-M.pdf</link>
    <guid isPermaLink="false">D4000 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:46:16 CDT</pubDate>
  </item>

  <item>
    <title>Element D4010 - Wet Standpipe and Sprinkler Systems - ODG070810</title>
    <description>
      Paragraph 2.01 J. 3. - Added requirement to provide isolation valves with tamper switches to accommodate servicing break tank fill valves. Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D4010-M.pdf</link>
    <guid isPermaLink="false">D4010 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:46:14 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 10 13 - Wet Standpipe and Sprinkler Systems - MS030410</title>
    <description>Paragraph 2.04 - Clarified acceptable piping materials. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2010%2013.doc</link>
    <guid isPermaLink="false">21 10 13 MS030410</guid>
    <pubDate>Thu, 04 Mar 2010 08:21:06 CDT</pubDate>
  </item>  
 
<item>
<title>CSI Division 21 - Fire Suppression, Section 21 10 13 - Wet Standpipe and Sprinkler Systems - MS031909</title>
<description>Paragraphs; 1.04 B and 1.05 A 1 - Removed FM Global and cited project fire protection consultant. 1.05 C 6 a - Added electronic submittal requirement and changed ACAD version to 2005. 1.07 A - Clarified location of sprinkler head cabinet. 2.02 A - Added Flexhead as an acceptable manufacturer. 2.04 A - Added microbiological coating requirement. 2.04 A 3 - Added exception for Flexhead. 3.01 F - Clarified head guard requirements. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2010%2013.doc</link>
<guid isPermaLink="false">21 10 13 MS031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:19 CDT</pubDate>
</item>

<item>
<title>CSI Division 21 - Fire Suppression, Section 21 10 14 - Wet Standpipe and Sprinkler Systems Renovation - MS031909</title>
<description>Paragraphs; 1.02 C - Added water flow test requirement. 1.04 B and 1.05 A 2 - Removed FM Global and cited project fire protection consultant. 1.05 C 5 - Added electronic submittal requirement and changed ACAD version to 2005. 1.07 A - Clarified location of sprinkler head cabinet. 2.02 A - Added Flexhead as an acceptable manufacturer. 2.03 A 4 - Changed 42 degrees to 40 degrees. 2.04 A - Added microbiological coating requirement. 3.02 E - Clarified head guard requirements. 3.02 L - Emphasized torque tightening requirements for bolts. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2010%2014.doc</link>
<guid isPermaLink="false">21 10 14 MS031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:18 CDT</pubDate>
</item>

<item>
<title>CSI Division 21 - Fire Suppression, Section 21 31 13 - Fire Pumps - MS031909</title>
<description>Removed FM Global and cited project fire protection consultant. Paragraphs 1.05 B; 1.06 A 1. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2031%2013.doc</link>
<guid isPermaLink="false">21 31 13 MS031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:17 CDT</pubDate>
</item>

<item>
<title>CSI Division 21 - Fire Suppression, Section 21 41 23 - Fire Water and Domestic Water Surge Tanks - MS031909</title>
<description>Removed FM Global and cited project fire protection consultant. Paragraphs 1.04 B; 1.05 A 1. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2041%2023.doc</link>
<guid isPermaLink="false">21 41 23 MS031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:16 CDT</pubDate>
</item>

<item>
<title>Element D4000 - Fire Protection General Design Guidelines - ODG031909</title>
<description>Paragraph 2.01 B. - Added statement requiring design to meet 100 percent sprinkled building criteria. Paragraphs 2.02 B,C and D. - Deleted explanations addressign elevator sprinkler protection.
 Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D4000-M.pdf</link>
<guid isPermaLink="false">D4000 ODG031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:15 CDT</pubDate>
</item>

<item>
<title>Element D400001 - Open Parking Garage General Design Guidelines - ODG031909</title>
<description>Paragraph 2.01 C. - Deleted manual standpipe protection, deleted references to NFPA 88A an IFC. Added reference to Element Z2005. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D400001-M.pdf</link>
<guid isPermaLink="false">D400001 ODG031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:14 CDT</pubDate>
</item>

<item>
<title>Element D4010 - Wet Standpipe and Sprinkler Systems - ODG031909</title>
<description>Paragraph 2.01 A. - Added reference to Element Z2005. Paragraph 2.01 B. - Changed 42 degrees to 40 degrees fahrenheit. Paragraph 2.01 I. - Added option for variable speed controllers. Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D4010-M.pdf</link>
<guid isPermaLink="false">D4010 ODG031909</guid>
<pubDate>Thu, 19 Mar 2009 07:14:13 CDT</pubDate>
</item>

<item>
<title>CSI Division 21 - Fire Suppression, Section 21 10 13 - Wet Standpipe and Sprinkler Systems - MS052208</title>
<description>Added requirement for minimum thickness of schedule 40 for piping.	2.04, A.
 Please direct Question or Comments to Bryan Galloy at 713-792-1284.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div21</link>
<guid isPermaLink="false">21 10 13 MS030408</guid>
<pubDate>Tue, 04 Mar 2008 10:10:14 CDT</pubDate>
</item>


-->
