  <item>
    <title>Element D201001 - Emergency Shower and Eye Wash Equipment - ODG041113</title>
    <description>
      Added drainage requirement for emergency equipment per request by EH&amp;S. Paragraph 2.01 P.
       - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D201001-M.pdf</link>
    <guid isPermaLink="false">D201001 ODG041113</guid>
    <pubDate>Thu, 11 Apr 2013 08:40:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D2060 - Medical Vacuum and Gas Systems - ODG111512</title>
    <description>
      2.04 G &amp; I – Deleted requirement for purge connections downstream of line shut-off valves.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D2060-M.pdf</link>
    <guid isPermaLink="false">D2060 ODG111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:40:25 CDT</pubDate>
  </item>

  <item>
    <title>Element D2065 - Laboratory Vacuum and Gas Systems - ODG111512</title>
    <description>
      2.04 F &amp; H – Deleted requirement for purge connections downstream of line shut-off valves.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D2065-M.pdf</link>
    <guid isPermaLink="false">D2065 ODG111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:40:24 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 05 33 - Domestic Hot Water Heat Maintenance Tracing - MS111512</title>
    <description>
      1.03 C. 3. - Updated NEC edition to 2011.
      - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2005%2033.doc</link>
    <guid isPermaLink="false">22 05 33 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:24 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS111512</title>
    <description>
      1.04 D. - Added requirement that all grooved joint couplings, fittings, flanges, valves, and tools of the same type shall be the products of a single manufacturer.
      1.05 A. 2. - Added requirement that grooved joint couplings and fittings product submittals shall specifically identified the applicable style or series designation.
      2.03 C. - Clarified grooved copper piping fitting and flange requirements. Added paragraphs C. 1 and 2.
      2.03 J. - Adde Anvil as an acceptable manufacturer for dielectric waterway fittings.
      2.04 D, E, F and G. -  Removed 2-1/2" and 3" Kitz ball valves. Revised to require that line shut-off valves larger than 2&quot; be butterfly type.
      2.04 K. - Added Tour &amp; Andersson/ Victaulic as an acceptable manufacturer for domestic hot water return balancing valves.
      2.05 A. - Added Tour &amp; Andersson/ Victaulic as an acceptable manufacturer for differintial pressure meters.
      3.03 D. 5. - Deleted the words &quot;to 80 inch pounds minimum or&quot;.
      3.03 6. - Reworded the paragraph to prevent misinterpretration and insure that tie-rod bracing is installed at all changes of direction in unburied roof drainage piping systems.
      3.05 A. &amp; B. - Added training requirements for copper press and copper grooved fitting installation.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:23 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 11 23 - Domestic Water Pressure Boosting Systems (VFD) - MS111512</title>
    <description>
      1.03 C. 3. - Updated NEC edition to 2011.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2011%2023.doc</link>
    <guid isPermaLink="false">22 11 23 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:22 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 11 24 - Domestic Water Pressure Boosting Systems (Constant Speed) - MS111512</title>
    <description>
      1.03 C. 3. - Updated NEC edition to 2011.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2011%2024.doc</link>
    <guid isPermaLink="false">22 11 24 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:21 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 31 16 - Domestic Water Softeners - MS111512</title>
    <description>
      1.03 C. 8. - Updated NEC edition to 2011.
      2.02 A. &amp; B. - Removed Unity, Bruner and Mueller manufacturers and added Watertech and Marlo.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2031%2016.doc</link>
    <guid isPermaLink="false">22 31 16 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:20 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 33 13 - Electric Instantaneous Domestic Water Heaters - MS111512</title>
    <description>
      1.03 C. 3. - Updated NEC edition to 2011.
       - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2033%2013.doc</link>
    <guid isPermaLink="false">22 33 13 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:19 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 33 33 - Electric Domestic Water Heaters (Point-of-Use, Storage Type) - MS111512</title>
    <description>
      1.03 C. 3. - Updated NEC edition to 2011.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2033%2033.doc</link>
    <guid isPermaLink="false">22 33 33 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:18 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS111512</title>
    <description>
      2.01 D. - Deleted Emergency Shower and Eyewash fixtures from Acceptable Manufacturers list.
      2.01 L. - Deleted TOTO as and acceptable manufacturer for lav/sink sensor faucets.
      2.02 Q. 10. &amp; 11. - Deleted TOTO sensor faucets and updated Chicago Faucet model numbers.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2040%2000.doc</link>
    <guid isPermaLink="false">22 40 00 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:17 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 67 13 - High Purity Water Systems (RO) - MS111512</title>
    <description>
      1.02 D. - Replaced manufacturer Bob Johnson and Associates with Marlo.
      1.03 C. 6. - Updated NEC edition to 2011.
      2.03 F. - Removed manufacturer Bruner and added Watertech, Marlo and Culligan.
      - Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2067%2013.doc</link>
    <guid isPermaLink="false">22 67 13 MS111512</guid>
    <pubDate>Thu, 15 Nov 2012 08:39:16 CDT</pubDate>
  </item>
    
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 53 - Laboratory Vacuum and Gas Piping - MS091312</title>
    <description>
      Added reference to NFPA 45 and added Patton's Medical as an acceptable manufacturer. Paragraph 1.03 C.1. and various locations within document.
       - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2053.doc</link>
    <guid isPermaLink="false">22 60 53 MS091312</guid>
    <pubDate>Thu, 13 Sep 2012 08:35:02 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 00 - Medical Vacuum and Gas Piping - MS082812</title>
    <description>
      Added Patton's Medical/Amico as an acceptable manufacturer for products addressed in this section. 2.04 C. 8. and 9. - added that zone valve boxes may house up to six valves and incorporate alarm sensor connection on each valve within box. 2.07 A. 9. - added that alarm sensors may be located within zone valve box. 3.01 R. - Added tha all alarm sensors shall be readily accessible.
      - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2000.doc</link>
    <guid isPermaLink="false">22 60 00 MS082812</guid>
    <pubDate>Tue, 28 Aug 2012 08:35:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 61 19 - Medical Air Compressor Systems - MS082812</title>
    <description>
      Clarified verification testing agency qualifications and added Patton's Medical/Hitachi as an acceptable packager. Paragraphs 1.04 E. and 2.01 K.
      - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2061%2019.doc</link>
    <guid isPermaLink="false">22 61 19 MS082812</guid>
    <pubDate>Tue, 28 Aug 2012 08:35:09 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS061912</title>
    <description>
      Revised secondary storm drainage piping that discharges onto face of exterior building wall to be CPVC drainage piping system meeting ASTM E 84 flame/smoke requirements. Paragraph 2.02 B.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS061912</guid>
    <pubDate>Tue, 19 Jun 2012 08:42:14 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 20 - Common Fire Suppression, Plumbing and HVAC Requirements, Section 20 05 29 - Supports and Sleeves - MS051712</title>
    <description>Added requirement to support individual non-insulated brass or copper lines 4 inch and smaller with adjustable swivel ring hangers. Paragraph 2.03 A.10. - Please direct Questions and Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div20/20%2005%2029.doc</link>
    <guid isPermaLink="false">20 05 29 MS051712</guid>
    <pubDate>Thu, 17 May 2012 08:24:12 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS041712</title>
    <description>
      Changed public toilet room lavatory faucet flow rate to 0.5 gpm and non-patient shower flow rate to 2.0 gpm. - Paragraph 2.02 L. and Q.11.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2040%2000.doc</link>
    <guid isPermaLink="false">22 40 00 MS041712</guid>
    <pubDate>Tue, 17 Apr 2012 08:23:15 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 20 - Common Fire Suppression, Plumbing and HVAC Requirements, Section 20 05 29 - Supports and Sleeves - MS041712</title>
    <description>Clarified that floor sleeve waterstop shall be located at slab midpoint. Paragraph 2.04 B.2. - Please direct Questions and Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div20/20%2005%2029.doc</link>
    <guid isPermaLink="false">20 05 29 MS041712</guid>
    <pubDate>Tue, 17 Apr 2012 08:23:14 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS040512</title>
    <description>
      Paragraph 2.02 G. - Revised no-hub clamp requirements by specifying Clamp-All 125 torq and Husky series 4000 assemblies for all cast iron pipe sizes.
      Paragraph 2.03 D. - Clarified where copper press fittings are allowed, deleted Elkhart and Nibco manufacturers and added requirement that contractor must obtain Owner's Property Manager approval prior to bidding.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS040512</guid>
    <pubDate>Thu, 05 Apr 2012 08:32:24 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS040512</title>
    <description>
      Paragraph 2.05 - Clarified that hub drains must be manufactured hubs and that field cut no-hub or plain-end pipe stub-ups are not acceptable.
      Paragraph 2.07 A. - Deleted requirement for 6 inch cleanouts and allow cleanouts to be the same nominal size as the pipe they serve up to four inches.
      Paragraph 2.13 - Revised to limit the use of trap seal protection inserts by allowing them only where job conditions prevent the installation of water supplied trap primers.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2030.doc</link>
    <guid isPermaLink="false">22 10 30 MS040512</guid>
    <pubDate>Thu, 05 Apr 2012 08:32:23 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 31 16 - Domestic Water Softeners - MS040512</title>
    <description>
      Added statement that regeneration shall be controlled by actual hardness or by a flow volume control that is based on the hardness of the water to be softened.	Paragraph 2.10 C.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2031%2016.doc</link>
    <guid isPermaLink="false">22 31 16 MS040512</guid>
    <pubDate>Thu, 05 Apr 2012 08:32:22 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS040512</title>
    <description>
      Added Plumberex as an acceptable manufacturer for ADA insulation kits.
      Changed water closet water usage to maximum 1.28 gallons per flush.
      Changed urinal water usage to maximum 0.25 gallons per flush.	Paragraphs 2.01 Y. and 2.02 L. 4. and 5.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2040%2000.doc</link>
    <guid isPermaLink="false">22 40 00 MS040512</guid>
    <pubDate>Thu, 05 Apr 2012 08:32:21 CDT</pubDate>
  </item>

  <item>
    <title>Element D2030 - Sanitary Waste and Vent - ODG040512</title>
    <description>
      Added requirements that restrict the use of trap seal protection inserts. Paragraph 2.01 P.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D2030-M.pdf</link>
    <guid isPermaLink="false">D2030 ODG040512</guid>
    <pubDate>Thu, 05 Apr 2012 08:32:10 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS011912</title>
    <description>
      Paragraph 3.03 C. 3. - Added requirement that all solder joints shall be wiped to remove paste residue and excess solder.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS011912</guid>
    <pubDate>Thu, 19 Jan 2012 08:45:26 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 00 - Medical Vacuum and Gas Piping - MS011912</title>
    <description>
      Paragraph 1.05 D. 4. - Changed brazer certification renewal requirement from one year to three years.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2000.doc</link>
    <guid isPermaLink="false">22 60 00 MS011912</guid>
    <pubDate>Thu, 19 Jan 2012 08:45:25 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 53 - Laboratory Vacuum and Gas Piping - MS011912</title>
    <description>
      Paragraph 1.05 D. 4. - Changed brazer certification renewal requirement from one year to three years.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2053.doc</link>
    <guid isPermaLink="false">22 60 53 MS011912</guid>
    <pubDate>Thu, 19 Jan 2012 08:45:24 CDT</pubDate>
  </item>


  <!--  
  
  
  <item>
    <title>Element D2000 - General Design Guidelines - ODG120811</title>
    <description>
      Paragraph 3.01 K. – Added requirement for coordinating with Architect and identifying components located within rated partitions and floors.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2000-M.pdf</link>
    <guid isPermaLink="false">D2000 ODG120811</guid>
    <pubDate>Thu, 08 Dec 2011 08:35:02 CDT</pubDate>
  </item>

  <item>
    <title>Element D2020 - Domestic Water Distribution - ODG081811</title>
    <description>
      2.01 F. – Revised ASHRAE table reference number.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r04/D2020-M.pdf</link>
    <guid isPermaLink="false">D2020 ODG081811</guid>
    <pubDate>Thu, 18 Aug 2011 08:36:15 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS080211</title>
    <description>
      Added requirements for verifying interior cleanliness of drainage, waste and vent piping. Paragraphs 3.04 B. 6. and 7.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS080211</guid>
    <pubDate>Tue, 02 Aug 2011 08:23:10 CDT</pubDate>
  </item>

  <item>
    <title>Supplemental Resources - Section 01 64 34 - Coffee Dispenser Utility Services - MS080211</title>
    <description>
      Revised model of backflow preventer required. - Paragraph 2.02 F.1.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/supp_stds/01%2064%2034.pdf</link>
    <guid isPermaLink="false">01 64 34 MS080211</guid>
    <pubDate>Tue, 02 Aug 2011 08:22:08 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS060211</title>
    <description>
      Added Watts as an acceptable manufacturer for dielectric unions and flanges. Paragraphs 2.03 K &amp; L.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS060211</guid>
    <pubDate>Thu, 02 Jun 2011 08:30:20 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS052411</title>
    <description>
      Paragraph 2.02 N. - Changed the word &quot;Janitor&quot; to &quot;Housekeeping&quot;. Added option for a 6&quot; front drop threashold on mop sinks when scheduled on Contract Drawings.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2040%2000.doc</link>
    <guid isPermaLink="false">22 40 00 MS052411</guid>
    <pubDate>Tue, 24 May 2011 08:21:40 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 00 - Medical Vacuum and Gas Piping - MS052411</title>
    <description>
      Paragraph 1.07 F. - Changed viability of certification for axially swaged fittings installation to 3 years.
      Paragraph 2.02 F. - Added option to use axially swaged fittings for connecting to existing pressurized medical gas piping.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2000.doc</link>
    <guid isPermaLink="false">22 60 00 MS052411</guid>
    <pubDate>Tue, 24 May 2011 08:21:38 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 53 - Laboratory Vacuum and Gas Piping - MS052411</title>
    <description>
      Paragraph 1.07 F. - Changed viability of certification for axially swaged fittings installation to 3 years.
      Paragraph 2.02 F. - Added option to use axially swaged fittings for connecting to existing pressurized laboratory gas piping.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2053.doc</link>
    <guid isPermaLink="false">22 60 53 MS052411</guid>
    <pubDate>Tue, 24 May 2011 08:21:36 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 66 53 - Laboratory Waste and Vent piping (PP/Duriron) - MS052411</title>
    <description>
      Paragraph 3.03 C. 19. - Changed 2&quot; to 3&quot; to address support spacing for 3&quot; diameter drain piping.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2066%2053.doc</link>
    <guid isPermaLink="false">22 66 53 MS052411</guid>
    <pubDate>Tue, 24 May 2011 08:21:34 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS051011</title>
    <description>
      Deleted requirement for sediment bucket in shower stall floor drains. Paragraph 2.03 E.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2030.doc</link>
    <guid isPermaLink="false">22 10 30 MS051011</guid>
    <pubDate>Tue, 10 May 2011 08:32:34 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS031711</title>
    <description>
      Added paragraph 3.03 C. 14. - Close nipples shall not be installed in plumbing piping systems.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:30:20 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 20 23 - Natural Gas Piping - MS031711</title>
    <description>
      Paragraph 3.03 T. - Added that close nipples are not permitted in gas piping systems.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2020%2023.doc</link>
    <guid isPermaLink="false">22 20 23 MS031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:30:18 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 00 - Medical Vacuum and Gas Piping - MS031711</title>
    <description>
      Paragraph 1.07 F. -	Installer of axially swaged fittings shall be certified by a recognized agency trained in administering axially swaged fitting installation techniques. Installation Contractor shall present written documentation of certification (less than 1 year old).
      2.03 D. - Close nipples shall not be installed.
      2.03 F. - The use of brass axially swaged, elastic strain preload fittings may be used when making connections to existing piping sizes 2” and smaller. Non-braze fittings shall provide metal to metal seal having pressure and temperature ratings not less than that of a brazed joint and when complete are permanent and nonseparable. Axially swaged fittings shall be cleaned and sealed for oxygen service and manufactured by Lokring Technology LLC.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2000.doc</link>
    <guid isPermaLink="false">22 60 00 MS031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:30:16 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 53 - Laboratory Vacuum and Gas Piping - MS031711</title>
    <description>
      Paragraph 1.07 F. -	Installer of axially swaged fittings shall be certified by a recognized agency trained in administering axially swaged fitting installation techniques. Installation Contractor shall present written documentation of certification (less than 1 year old).
      2.03 D. - Close nipples shall not be installed.
      2.03 F. - The use of brass axially swaged, elastic strain preload fittings may be used when making connections to existing piping sizes 2” and smaller. Non-braze fittings shall provide metal to metal seal having pressure and temperature ratings not less than that of a brazed joint and when complete are permanent and nonseparable. Axially swaged fittings shall be cleaned and sealed for oxygen service and manufactured by Lokring Technology LLC.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2053.doc</link>
    <guid isPermaLink="false">22 60 53 MS031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:30:14 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 62 19 - Medical Vacuum Pump Systems - MS031711</title>
    <description>
      Changed pump type from &quot;Dynamic&quot; to &quot;Rotary Claw&quot;. Paragraphs 2.01 through 2.04.
      Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2062%2019.doc</link>
    <guid isPermaLink="false">22 62 19 MS031711</guid>
    <pubDate>Thu, 17 Mar 2011 08:30:12 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS020311</title>
    <description>
      Paragraph 3.03 F. 7. - Added requirement to provide a shutoff valve immediately upstream of each strainer. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS020311</guid>
    <pubDate>Thu, 03 Feb 2011 08:36:09 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS020311</title>
    <description>
      Paragraph 3.02 C. 4. - Deleted the words &quot;Backflow preventer&quot;.
      Paragraph 3.02 C. 5. - Added the words &quot;or backflow preventers&quot;.
      Paragraph 3.02 C. 6. - Added requirement to install a strainer immediately upstream of each vacuum breaker and backflow preventer. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 30 MS020311</guid>
    <pubDate>Thu, 03 Feb 2011 08:36:07 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS020311</title>
    <description>
      Paragraph 2.02 N. 5. - Changed caulked lead connection to code compliant connection.
      Paragraph 2.02 Q. 3. - Added requirements that gooseneck spout outlets shall terminate five inches minimum and five &amp; one half inches maximum above top rim of lavatory or sink. Horizontal dimension from spout inlet to spout outlet shall be a minimum five &amp; one half inches. Previous requirement was five inches minimum and seven inches maximum.
      - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2040%2000.doc</link>
    <guid isPermaLink="false">22 40 00 MS020311</guid>
    <pubDate>Thu, 03 Feb 2011 08:36:05 CDT</pubDate>
  </item>
     
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS111110</title>
    <description>
      Clarified that emergency roof drain overflow piping that discharges at grade does not require internal epoxy lining. Paragraph 2.02 B. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS111110</guid>
    <pubDate>Thu, 11 Nov 2010 08:37:14 CDT</pubDate>
  </item>

  <item>
    <title>Element D2040 - Storm Water Drainage - ODG111110</title>
    <description>
      Included option to terminate emergency overflow piping immediately below the roof level or at grade and limited the size of overflow piping to 8” - Paragraph 2.01 B.
      Added requirement that emergency overflow piping terminals must be detailed on construction drawings – Paragraph 3.01 G.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D2040-M.pdf</link>
    <guid isPermaLink="false">D2040 ODG111110</guid>
    <pubDate>Thu, 11 Nov 2010 08:37:12 CDT</pubDate>
  </item> 
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 43 62 23 - Vacuum Insulated Pipe - MS110210</title>
    <description>Moved to Division 43 and re-numbered section as 43 62 23. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div43/43%2062%2023.doc</link>
    <guid isPermaLink="false">43 62 23 MS110210</guid>
    <pubDate>Tue, 02 Nov 2010 08:33:45 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 41 23 - Fire Water and Domestic Water Surge Tanks - MS101410</title>
    <description>
      Replaced tank exterior coating manufacturer Aegeon with Ameron. Paragraphs 2.02 B., 2.04 F and G.
      Revised requirement for dividing domestic water compartment to only when storage exceeds 2000 gallons. Paragraph 2.03 A. 1.b.
      Changed stilling well to interior stilling baffle. Paragraph 2.03 A. 3.o. - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2041%2023.doc</link>
    <guid isPermaLink="false">21 41 23 MS101410</guid>
    <pubDate>Thu, 14 Oct 2010 08:33:19 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 20 23 - Natural Gas Piping - MS101410</title>
    <description>
      2.06 A. - Added right and left hand nipple-coupling assemblies to approved types of unions.
      2.06 B. - Deleted the manufacturer name Epco.
      3.03 N. - Added requirement that right and left nipples couplings are to be used where unions are needed with the exception that ground joint type, flanges and appliance connectors may be used at equipment connections. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2020%2023.doc</link>
    <guid isPermaLink="false">22 20 23 MS101410</guid>
    <pubDate>Thu, 14 Oct 2010 08:33:17 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 20 - Common Fire Suppression, Plumbing and HVAC Requirements, Section 20 05 53 - Piping and Equipment Identification - MS101410</title>
    <description>
      Added requirement to identify right/left nipple/coupling union assemblies. Paragraph 3.03 N. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div20/20%2005%2053.doc</link>
    <guid isPermaLink="false">20 05 53 MS101410</guid>
    <pubDate>Thu, 14 Oct 2010 08:33:15 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS100510</title>
    <description>
      Added requirement that secondary (emergency overflow) roof drain piping shall be internally lined with 1/8 inch thick epoxy for corrosion protection. Paragraph 2.02 B. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS100510</guid>
    <pubDate>Tue, 05 Oct 2010 08:20:20 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS100510</title>
    <description>
      Added requirement that secondary (emergency overflow) roof drains are to be epoxy coated. Paragraphs 2.06 B. - Please direct Questions or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2030.doc</link>
    <guid isPermaLink="false">22 10 30 MS100510</guid>
    <pubDate>Tue, 05 Oct 2010 08:20:18 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS093010</title>
    <description>
      Added requirement that all ball and butterfly line shut-off valves are to be provided with lockable handles. Paragraphs 2.04 D. E. F. G. &amp; H. - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS093010</guid>
    <pubDate>Thu, 30 Sep 2010 08:30:22 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS093010</title>
    <description>
      Changed requirement for 6 inch diameter gauges to be provided when installed above eight feet from floor (previously six feet).	Paragraphs 2.16 C. &amp; 2.17 A. - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2030.doc</link>
    <guid isPermaLink="false">22 10 30 MS093010</guid>
    <pubDate>Thu, 30 Sep 2010 08:30:20 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 21 - Fire Suppression, Section 21 41 23 - Fire Water and Domestic Water Surge Tanks - MS093010</title>
    <description>
      Significant revisions throughout document. Majority of changes related to fill valves and tank coatings. - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div21/21%2041%2023.doc</link>
    <guid isPermaLink="false">21 41 23 MS093010</guid>
    <pubDate>Thu, 30 Sep 2010 08:30:18 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D2020 - Domestic Water Distribution - ODG091610</title>
    <description>
      2.01, I. ; Included additional hose bib provisions for roof maintenance purposes.
      2.03, F., 3., 5. And 6. ; Included additional requirements for domestic water surge tank fill valves.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D2020-M.pdf</link>
    <guid isPermaLink="false">D2020 ODG091610</guid>
    <pubDate>Thu, 16 Sep 2010 08:31:15 CDT</pubDate>
  </item>  

  <item>
    <title>CSI Division 11 - Equipment, Section 11 53 13 - Chemical Fume Hoods and Biological Safety Cabinets - MS081210</title>
    <description>Added statement forbidding installation of vacuum breakers within hood. Deleted plumbing fitting model numbers and referenced Contract Drawings for fittings schedule. Paragraphs 2.02 B. and F. - Please direct Questions and Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div11/11%2053%2013.doc</link>
    <guid isPermaLink="false">11 53 13 MS081210</guid>
    <pubDate>Thu, 12 Aug 2010 08:35:07 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS072210</title>
    <description>
      1.04 C. ; Deleted requirement that &quot;All pipe, fittings, couplings, gaskets and valves shall be manufactured domestically.&quot;
      Deleted paragraph 3.04 B. 4. which addressed plumbing fixture testing. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:31:26 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS072210</title>
    <description>
      Added article 2.12 to specify hose bibb types for general use and housekeeping mop sink use. Deleted paragraph 3.02 F. for editorial purposes. - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2030.doc</link>
    <guid isPermaLink="false">22 10 30 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:31:24 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS072210</title>
    <description>
      2.02 M. 3. ; Added requirement that sink strainers shall be 316 stainless steel. 2.02 Q. 2. ; Added the words "threaded or serrated" before hose connection outlets. 2.02 Q. 3. ; Replaced the word &quot;janitor's&quot; with &quot;mixing type&quot;. 3.05 C. ; Added &quot;Each fixture shall be filled and then drained. Traps and fixture connections shall be proven water tight by visual inspection.&quot; - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2040%2000.doc</link>
    <guid isPermaLink="false">22 40 00 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:31:22 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 60 53 - Laboratory Vacuum and Gas Piping - MS072210</title>
    <description>
      Deleted references and requirements throughout document related to waste anesthesia gas disposal and nitrous oxide. - Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2053.doc</link>
    <guid isPermaLink="false">22 60 53 MS072210</guid>
    <pubDate>Thu, 22 Jul 2010 08:31:20 CDT</pubDate>
  </item>

  <item>
    <title>Supplemental Resources - Plumbing Installation Details - PL072010</title>
    <description>
      Added Plumbing detail for Housekeeping Mop Sink Water Outlets.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/details/pl-224000-01.pdf</link>
    <guid isPermaLink="false">PL-224000-01 070810</guid>
    <pubDate>Tue, 20 Jul 2010 08:49:24 CDT</pubDate>
  </item>

  <item>
    <title>Element D2010 - Plumbing Fixtures - ODG070810</title>
    <description>
      4.03 P. ; Added requirement that housekeeping mop sinks shall be provided with RPZ backflow preventer protected hose bibbs in lieu of the &quot;standard&quot; mixing faucet.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r03/D2010-M.pdf</link>
    <guid isPermaLink="false">D2010 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:47:22 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D2020 - Domestic Water Distribution - ODG070810</title>
    <description>
      2.02 B. ; Deleted statement concerning municipal systems.
      2.03 F. 4. ; Added requirement to provide isolation valves for each water storage tank fill valve for servicing purposes.
      2.03 F. 5. ; Added requirement to provide blind flanged valves for future break tank bypass for servicing purposes.
      2.04 A. 1. a. &amp; b. ; Added requirement to circulate hot water piping to within 18 inches of  public lavatory faucets and clarified maximum length of piping from point-of-use instantaneous heaters.
      2.04 C. 1.  ; Added statement that separate water heaters and circulation pumps should be considered for serving processes and equipment that require water temperatures in excess of 110 degrees F.
      2.04 C. 2. ; Added statement that separate water heaters and circulation pumps are required for each pressure zone within a building.
      2.04 F. ; Added statement that Water heating equipment shall not be subjected to system pressures beyond its its ASME stamped working pressure.
      2.05 C. ; Added requirement to serve multiple centralized equipment with one set of duplexed backflow preventers rather than individual backflow preventers at each piece of equipment.
      2.05 I. ; Added statement to prevent dead-legs in piping due to installing shock absorbers with pipe extensions.
      3.01 C. and E. ; Clarified requirements to provide hot water return circuit setters/balancing valve information on drawings. 
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D2020-M.pdf</link>
    <guid isPermaLink="false">D2020 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:47:20 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D2065 - Laboratory Vacuum and Gas Systems - ODG070810</title>
    <description>
      2.01 G. ; Changed vacuum level from 25 to 19 inches of mercury (Hg).
      2.04 I. ; Added requirement for metering carbon dioxide usage. 
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2065-M.pdf</link>
    <guid isPermaLink="false">D2065 ODG070810</guid>
    <pubDate>Thu, 08 Jul 2010 08:47:18 CDT</pubDate>
  </item>  
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 62 23 - Vacuum Insulated Pipe - MS042210</title>
    <description>Initial Issue of Section. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2062%2023.doc</link>
    <guid isPermaLink="false">22 62 23 MS042210</guid>
    <pubDate>Thu, 22 Apr 2010 08:53:26 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS030410</title>
    <description>2.01C.; Added &quot;and temperature&quot;. 2.02 E.; Added &quot;and temperature&quot;. 2.02 F.; Added Cla-Val. 2.08; Added (INCLUDES BACKPRESSURE AND BACKSIPHONAGE). 2.08 E. 1.; Revised ASSE standard reference. 2.08 E. 7.; Deleted sizes one and one quarter inches through two inches. 2.08 F.; Added dual check valves for carbonated beverage dispensers. 2.09; Changed water pressure regulating valve requirements. 2.13; Deleted line pressure activated trap primers and added electronic trap priming devices. 3.02; Added installation requirements for backflow and backsiphonage devices, water pressure regulators and trap primers. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2030.doc</link>
    <guid isPermaLink="false">22 10 30 MS030410</guid>
    <pubDate>Thu, 04 Mar 2010 08:18:18 CDT</pubDate>
  </item>  
  
  <item>
    <title>Element D2020 - Domestic Water Distribution - ODG030210</title>
    <description>
      Changed City of Houston to municipality. Paragraph 2.01 B. ;  Added requirement for electronic trap primers. Paragraph 2.01 P. ;  Included additional requirements for pressure regulators. Paragraphs 2.02 C,D &amp; E. ; Clarified system size parameters for use of VFD booster pump control. Paragraphs 2.03 B, C &amp; D. ; Included additional requirements for backflow and backsiphonage devices. Paragraphs 2.05 C, D, E, F &amp; G.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2020-M.pdf</link>
    <guid isPermaLink="false">D2020 ODG030210</guid>
    <pubDate>Tue, 02 Mar 2010 08:17:24 CDT</pubDate>
  </item>

  <item>
    <title>Element D2030 - Sanitary Waste and Vent - ODG030210</title>
    <description>
      Added requirement for proper design of evacuating equipment and relief valve discharge. Paragraph 2.01 R.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D2030-M.pdf</link>
    <guid isPermaLink="false">D2030 ODG030210</guid>
    <pubDate>Tue, 02 Mar 2010 08:17:22 CDT</pubDate>
  </item>

  <item>
    <title>Element D2060 - Medical Vacuum and Gas Systems - ODG030210</title>
    <description>
      Changed NFPA standard reference for bulk oxygen storage from 50 to 55. Paragraphs 2.01 A. and 2.02 H.
      Clarified minimum size requirements for pressure gases and vacuum piping. Paragraph 2.04 E.
      Please direct Questions and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2060-M.pdf</link>
    <guid isPermaLink="false">D2060 ODG030210</guid>
    <pubDate>Tue, 02 Mar 2010 08:17:20 CDT</pubDate>
  </item>
 
  <item>
    <title>CSI Division 22 - Plumbing, Various Sections - MS120109</title>
    <description>
      Changed referenced edition of the International Plumbing Code from 2006 to 2009. Changed referenced edition of the National Electric Code from 2005 to 2008. Deleted all version references for NFPA 99. - Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs.html#div22</link>
    <guid isPermaLink="false">div22 MS120109</guid>
    <pubDate>Tue, 01 Dec 2009 08:04:09 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 14 29 - Elevator Pit Sump Pumps - MS120109</title>
    <description>
      Deleted section due to change in Code requirements. - Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs.html#div22</link>
    <guid isPermaLink="false">22 14 29 MS120109</guid>
    <pubDate>Tue, 01 Dec 2009 08:04:05 CDT</pubDate>
  </item>
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 10 00 - Plumbing Piping - MS111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraphs 3.03 D. 7 &amp; 8. 
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2010%2000.doc</link>
    <guid isPermaLink="false">22 10 00 MS111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:14 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 35 23 - Semi-Instantaneous Domestic Water Heaters (Hot Water) - MS111009</title>
    <description>
      Added RECO as an acceptable manufacturer. Paragraph 2.02 A.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2035%2023.doc</link>
    <guid isPermaLink="false">22 35 23 MS111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:13 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 35 24 - Semi-Instantaneous Domestic Water Heaters (Steam) - MS111009</title>
    <description>
      Added RECO as an acceptable manufacturer. Paragraph 2.02 A.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2035%2024.doc</link>
    <guid isPermaLink="false">22 35 24 MS111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:12 CDT</pubDate>
  </item>
  
  <item>
    <title>CSI Division 22 - Plumbing, Section 22 66 53 - Laboratory Waste and Vent piping (PP/Duriron) - MS111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraph 3.03 C. 22.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2066%2053.doc</link>
    <guid isPermaLink="false">22 66 53 MS111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:10 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 66 54 - Laboratory Waste and Vent piping (Glass/Duriron) - MS111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraph 3.03 C. 22.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2066%2054.doc</link>
    <guid isPermaLink="false">22 66 54 MS111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:09 CDT</pubDate>
  </item>


  <item>
    <title>CSI Division 22 - Plumbing, Section 22 66 55 - Laboratory Waste and Vent piping (Duriron) - MS111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraph 3.03 C. 21.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2066%2055.doc</link>
    <guid isPermaLink="false">22 66 55 MS111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:08 CDT</pubDate>
  </item>

  <item>
    <title>Element D2030 - Sanitary Waste and Vent - ODG111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet) and added verbiage regarding cleanout locations to match master specifications. Paragraph 2.01 G.
      Revised elevator pit sump pumping requirements to comply with the 2007 edition of ASME A17.1. Paragraph 2.01 Q.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2030-M.pdf</link>
    <guid isPermaLink="false">D2030 ODG111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:07 CDT</pubDate>
  </item>

  <item>
    <title>Element D2035 - Laboratory Waste and Vent - ODG111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet) and added verbiage regarding cleanout locations to match master specifications. Paragraph 2.01 L.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2035-M.pdf</link>
    <guid isPermaLink="false">D2035 ODG111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:06 CDT</pubDate>
  </item>

  <item>
    <title>Element D2040 - Storm Water Drainage - ODG111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraph 2.01 F.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D2040-M.pdf</link>
    <guid isPermaLink="false">D2040 ODG111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:05 CDT</pubDate>
  </item>

  <item>
    <title>Element D203001 - Sanitary Waste and Vent for Open Parking Garages - ODG111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraph 2.01 F.
      Revised elevator pit sump pumping requirements to comply with the 2007 edition of ASME A17.1. Paragraph 2.01 N.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D203001-M.pdf</link>
    <guid isPermaLink="false">D203001 ODG111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:04 CDT</pubDate>
  </item>

  <item>
    <title>Element D204001 - Storm Water Drainage for Open Parking Garages - ODG111009</title>
    <description>
      Changed maximum distance between cleanouts in horizontal drainage piping to 75 feet (previously 90 feet). Paragraph 2.01 D.
      Please direct Question or Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r01/D204001-M.pdf</link>
    <guid isPermaLink="false">D204001 ODG111009</guid>
    <pubDate>Tue, 10 Nov 2009 07:50:03 CDT</pubDate>
  </item>

  <item>
    <title>CSI Division 22 - Plumbing, Section 22 20 23 - Natural Gas Piping - MS101509</title>
    <description>
      Clarified the type of natural gas piping required to prevent the installation of small diameter seamed furnace welded pipe.Changed the requirement for encasing concealed gas piping that is installed within a building. The change requires only concealed threaded piping to be encased. Welded piping would not need to be encased. Added chases, walls and non-accessible locations as places where valves, unions, etc. should not be installed. Paragraphs 2.02 B., C. &amp; D. and 3.03 P.
      Please direct Question and Comments to David Spain at 713-792-8685.
    </description>
    <link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2020%2023.doc</link>
    <guid isPermaLink="false">22 20 23 MS101509</guid>
    <pubDate>Thu, 15 Oct 2009 07:51:14 CDT</pubDate>
  </item>  
  
<item>
<title>CSI Division 22 - Plumbing, Section 22 60 00 - Medical Vacuum and Gas Piping - MS091009</title>
<description>Added &quot;Hot-Tapping&quot; procedure. Paragraph 1.08. - Please direct Questions or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2000.doc</link>
<guid isPermaLink="false">22 60 00 MS091009</guid>
<pubDate>Thu, 10 Sep 2009 09:11:01 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 60 53 - Laboratory Vacuum and Gas Piping - MS091009</title>
<description>Added &quot;Hot-Tapping&quot; procedure. Paragraph 1.08. - Please direct Questions or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div22/22%2060%2053.doc</link>
<guid isPermaLink="false">22 60 53 MS091009</guid>
<pubDate>Thu, 10 Sep 2009 09:11:00 CDT</pubDate>
</item>

<item>
<title>CSI Division 20 - Common Fire Suppression, Plumbing and HVAC Requirements, Section 20 05 29 - Supports and Sleeves - MS072309</title>
<description>Added the word &quot;Cooper&quot; in front of B-Line, added C&amp;S Mfg. Corp. and Hubbard Enterprises Holdright as acceptable pipe support manufacturers. Clarified the materials and methods required to support plumbing service piping within chases and partitions. Paragraphs 2.02, A, 3,4 &amp; 5; 2.03, G. - Please direct Questions and Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div20/20%2005%2029.doc</link>
<guid isPermaLink="false">20 05 29 MS072309</guid>
<pubDate>Thu, 23 Jul 2009 07:23:42 CDT</pubDate>
</item>

<item>
<title>CSI Division 20 - Common Fire Suppression, Plumbing and HVAC Requirements, Section 20 05 53 - Piping and Equipment Identification - MS072309</title>
<description>Added International Plumbing Code to reference standards. Deleted sentence &quot;Verify with Drawings for all HVAC and plumbing systems for sizes.&quot; Clarified size of pipe requiring identification. Added Gray Water and Non-Potable water to Attachment A. Paragraphs 1.03 C 5, 2.05 C, 2.05 D and Attachment A. - Please direct Questions and Comments to Jim Dall at 713-792-5985.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs/div20/20%2005%2053.doc</link>
<guid isPermaLink="false">20 05 53 MS072309</guid>
<pubDate>Thu, 23 Jul 2009 07:23:40 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 11 23 - Domestic Water Pressure Boosting Systems - VFD - MS092508</title>
<description>Added 5 H.P. and Greater to the section title. - Please direct Questions or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 11 23 MS092508</guid>
<pubDate>Thu, 25 Sep 2008 09:10:16 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 11 24 - Domestic Water Pressure Boosting Systems - Constant Speed - MS092508</title>
<description>Added 3.5 H.P. and Less to the section title. - Please direct Questions or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 11 24 MS092508</guid>
<pubDate>Thu, 25 Sep 2008 09:10:15 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 66 56 - Laboratory Waste and Vent Piping (CPVC/Duriron) - MS091807</title>
<description>Deleted entire document - Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 66 56 MS091807</guid>
<pubDate>Thu, 11 Sep 2008 09:14:22 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 10 30 - Plumbing Specialties - MS080508</title>
<description>Updated backflow preventers product descrptive information. Added Double check valve assembly description and model numbers. Added duplex backflow preventer installation requirement for critical water services. Paragraphs 2.08, A,B,C,D,E; 3.02, K. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 10 30 MS080508</guid>
<pubDate>Tue, 05 Aug 2008 09:07:25 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 31 16 - Water Softeners - MS080508</title>
<description>Clarified backflow prevention requirements for water softener supply and drain piping. Paragraph 3.01, D. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 31 16 MS080508</guid>
<pubDate>Tue, 05 Aug 2008 09:07:24 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 40 00 - Plumbing Fixtures - MS073108</title>
<description>Added Chicago Hytronic lavatory and sink sensor faucets as acceptable products, added requirement for 500 pound load rated water closet carriers,  made various fixture type clarifications. Paragraphs 1.03,C.,8.; 2.01; 2.02,N.; 2.02,O.,4.; 2.02,Q.2.; 2.02,Q.5.; 2.02,Q.8.,9. and 10.; 2.02,R. - Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 40 00 MS073108</guid>
<pubDate>Thu, 31 Jul 2008 08:02:16 CDT</pubDate>
</item>

<item>
<title>Element D2010 - Plumbing Fixtures - ODG073108</title>
<description>Deleted reference to quiet action diaphragm and filtered bypass type flush valve - Paragraphs 4.04,D. and 4.05,B.; Added the word the non-ambulatory - Paragraph 4.04,E.
 Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/odg_archives/odg_r02/D2010-M.pdf</link>
<guid isPermaLink="false">D2010 ODG073108</guid>
<pubDate>Thu, 31 Jul 2008 08:02:14 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 20 23 - Natural Gas Piping - MS071508</title>
<description>Clarified test pressure for natural gas piping system having operating pressures between 0.5 and 5.0 psi. Paragraph 3.05, D.2.
 Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 20 23 MS071508</guid>
<pubDate>Tue, 15 Jul 2008 09:11:15 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 11 23 - Domestic Water Pressure Boosting Systems - VFD - MS051308</title>
<description>Added NSF61 reference; Clarified single source responsibilities; Added third-party cerification requirement; added submittal requirements for code compliance and third-party certification; Added requirement for spare VFD; Added Warranty paragraph; Added maximum zinc content; Added Namco and Grundfos to acceptable manufactures; Deleted VFD bypass requirement; Changed hydro-pneumatic tank connection to top; Added tank temperature limit; Added tank exterior paint requirement. Paragraphs 1.03, 5.; 1.04, A and F.; 1.05, A, 2 and 3; 1.07; 1.08; 2.01, B and C.; 2.02, A.; 2.04, F.; 2.08, A, B and C.
 Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 11 23 MS051308</guid>
<pubDate>Tue, 13 May 2008 10:10:14 CDT</pubDate>
</item>

<item>
<title>CSI Division 22 - Plumbing, Section 22 11 24 - Domestic Water Pressure Boosting Systems - Constant Speed - MS051308</title>
<description>Added NSF61 reference; Clarified single source responsibilities; Added third-party cerification requirement; added submittal requirements for code compliance and third-party certification; Added Warranty paragraph; Added maximum zinc content; Added Namco and Grundfos to acceptable manufactures; Added tank temperature limit; Added tank exterior paint requirement. Paragraphs 1.03, 5.; 1.04, A and F.; 1.05, A, 2 and 3; 1.07; 2.01, B and C.; 2.02, A.; 2.07, B and C.
 Please direct Question or Comments to David Spain at 713-792-8685.</description>
<link>http://www2.mdanderson.org/depts/cpm/standards/specs.htm#div22</link>
<guid isPermaLink="false">22 11 24 MS051308</guid>
<pubDate>Tue, 13 May 2008 10:10:12 CDT</pubDate>
</item>

-->
